Experimental Investigation of the Refrigerant Flow Distribution Characteristic of Heat Exchangers on the Residential Heat Pump Air Conditioner System Performance

Xiaoping Tu, Xiangfei Liang, Ruiqi Yang, Rong ZhuangPurdue 2016

Abstract

In this study, the refrigerant flow distribution characteristic of fin-and-tube heat exchanger used as outdoor and indoor heat exchanger of a residential heat pump air-conditioner was experimentally studied and analyzed. The outdoor heat exchanger included “n shape” 1-circuit, 2-circuit and 3-circuit arrangements, and the indoor heat exchanger was only “n shape” 2–ciucuit arrangement. It showed that the refrigerant flow distribution of both outdoor and indoor heat exchanger as evaporator would give much more system performance change of the residential heat pump air-conditioner than that as condenser. The refrigerant flow distribution characteristic can be expressed with the difference value of each circuit exit superheat as evaporator. The maximum difference value with little effect on system performance had been obtained both under cooling mode and heating mode. The maximum difference value was nearly the same at various test conditions and can be considered as 3℃. According to the experimental results, the system performance under heating mode especially for rated heating mode had more sensitive with refrigerant flow distribution characteristic than that under cooling mode, therefore the adjustment of refrigerant distribution characteristic of both the outdoor and indoor heat exchanger should mainly base on the rated heating mode.

Introduction

Modern residential heat pumps utilize fin-and-tube heat exchangers with multiple parallel circuits to optimize heat transfer while minimizing pressure drops. However, achieving uniform refrigerant distribution across these circuits is a significant engineering challenge. Factors such as gravity, complex pipe geometries, and non-uniform airflow often lead to "mal-distribution," where some circuits are flooded with liquid while others are starved. This study investigates the systemic impact of such imbalances on the performance of a complete R32 residential heat pump system under various operating conditions, moving beyond isolated component analysis to a "big picture" system view.

Experimental Methodology

The research was conducted using a 3500W R32 residential heat pump installed in a sophisticated test facility featuring indoor and outdoor environmental chambers. Performance was measured using the air enthalpy-difference method, tracking how Capacity and Coefficient of Performance (COP) deviated from a perfectly balanced baseline under standard operating conditions (GB/T 7725-2004).

Schematic of the experimental setup featuring indoor and outdoor environmental chambers.

To precisely control and measure refrigerant flow, the researchers modified the standard unit by installing individual Electronic Expansion Valves (EEVs) on each circuit of the indoor and outdoor heat exchangers. This allowed for the intentional induction of specific levels of flow imbalance across various configurations, including 1-circuit, 2-circuit, and 3-circuit arrangements for the outdoor unit.

Circuit arrangements for the heat exchangers, illustrating the use of individual EEVs for flow control.

Results and Discussion

The experimental data revealed that system performance is highly sensitive to flow distribution when the heat exchanger operates as an evaporator (the indoor unit during cooling, or the outdoor unit during heating). Mal-distribution in the evaporator forces the mixing of superheated gas from one branch with un-evaporated liquid from another, which is thermodynamically inefficient.

Key Findings

  • Heating Mode Sensitivity: The system is notably more sensitive to mal-distribution during heating than cooling. In rated heating mode, severe imbalance resulted in a capacity loss of up to 26% and a COP reduction of 14%. Consequently, engineers should prioritize flow-balancing specifically for the rated heating mode.
  • The 3°C Threshold: A critical observation across test conditions was that maintaining a temperature difference (TD) of less than 3°C (3K) between the refrigerant exits of different circuits results in negligible performance loss. Beyond this threshold, degradation accelerates rapidly.
  • Load and Complexity: Mal-distribution is particularly detrimental at intermediate (low-load) conditions due to lower mass flow rates. Furthermore, systems with more circuits (e.g., 3-circuit vs. 2-circuit) are more prone to imbalance as the lower flow rate in individual branches makes uniform distribution harder to maintain.

Conclusion

This study underscores the importance of optimizing refrigerant flow distribution to maintain residential heat pump efficiency. The identified 3°C exit temperature difference serves as a practical "sweet spot" target for design. Future work should focus on translating these findings into the development of better passive distributors capable of maintaining this balance without the cost of multiple electronic valves, particularly under real-world conditions like outdoor coil frosting.

Summary updated

Abstract

In this study, the refrigerant flow distribution characteristic of fin-and-tube heat exchanger used as outdoor and indoor heat exchanger of a residential heat pump air-conditioner was experimentally studied and analyzed. The outdoor heat exchanger included “n shape” 1 -circuit, 2-circuit and 3-circuit arrangements, and the indoor heat exchanger was only “n shape” 2–ciucuit arrangement. It showed that the refrigerant flow distribution of both outdoor and indoor heat exchanger as evaporator would give much more system performance change of the residential heat pump air-conditioner than that as condenser. The refrigerant flow distribution characteristic can be expressed with the difference value of each circuit exit superheat as evaporator. The maximum difference value with little effect on system performance had been obtained both under cooling mode and heating mode. The maximum difference value was nearly the same at various test conditions and can be considered as 3℃. According to the experimental results, the system performance under heating mode especially for rated heating mode had more sensitive with refrigerant flow distribution characteristic than that under cooling mode, therefore the adjustment of refrigerant distribution characteristic of both the outdoor and indoor heat exchanger should mainly base on the rated heating mode.