Experimental and Numerical Study on Thermal Performance of a Novel Direct Expansion Air-Source Heat Pump Heating System

Haobo Wang, Yuanda Cheng, Dawei Wang, Weijin Peng, Zejian Ai, Jie Jia, Pengfei Duan, J.‐m. YangFrontiers in Energy Research 2022 · DOI

Abstract

In this paper, a novel direct expansion air-source heat pump heating system with a gravity-driven radiator as a heating terminal was developed, for the purpose of reducing the energy consumption and improving the thermal comfort of indoor personnel. The thermal response speed of the system at the start-up stage was experimentally studied firstly. The results showed that the thermal response speed of the developed system was slightly lower than that of a traditional air-source heat pump heating system with a convective heating terminal, but largely higher than that of an air-source heat pump floor radiant heating system. When the outdoor air temperature fluctuated between −5.2 °C and −1.0 °C, the average rising ratios of indoor air temperature at the start-up stage for the developed heating system and the traditional system are 10.8 °C/h and 13.8 °C/h respectively. On this basis, an optimization study was then conducted to further improve the thermal performance of the developed heating system. The numerical results indicated that integrating a cross-flow fan to the gravity-driven radiator is able to promote the thermal performance of the heating system obviously at the start-up stage, because the convection heat transfer of the radiator was highly enhanced. Among the simulation conditions, the time required for the air temperature at head height to reach the designed temperature is shortest when the flow angle of the fan is 0° with an air speed of 0.6 m/s, while setting the flow angle of the fan to −45° with an air speed of 0.4 m/s is recommended to achieve the most thermal comfort for the whole body.

Introduction

Heating accounts for approximately 21% of building energy consumption in northern China. While air-source heat pumps (ASHPs) are a popular green solution, existing terminal units present significant trade-offs. Fan-coil or convective units heat rooms quickly but often cause discomfort due to drafts and noise. Conversely, radiant floor heating provides excellent comfort but suffers from high thermal inertia, taking hours to warm up. This makes floor heating inefficient for intermittent usage patterns common in residential and office buildings. This study introduces a novel "middle ground" terminal: a gravity-driven radiator that combines the comfort of radiation with a thermal response fast enough for modern intermittent heating.

Methodology

The research employed a two-pronged approach involving experimental validation and numerical optimization.

Experimental Setup

Two identical test rooms were established in Taiyuan, China. Room A utilized the novel gravity-driven radiators, while Room B served as a control with a standard cabinet air conditioner. The novel radiator employs thermosyphon heat pipe technology: refrigerant from the heat pump heats a working medium (alkyl dichloride) inside the radiator, which then circulates via gravity to release heat through radiation and natural convection.

Schematic of the direct expansion air-source heat pump system and gravity-driven radiator.

Numerical Optimization (CFD)

To enhance start-up speed, Computational Fluid Dynamics (CFD) was used to simulate an upgraded radiator equipped with a cross-flow fan. Twelve working conditions were tested, varying air supply angles (-45° to 90°) and speeds (0.2 to 0.6 m/s) to optimize the balance between rapid heating and occupant comfort. The CFD model was validated against experimental data, achieving a Root Mean Square Error (RMSE) of 21%, well within engineering standards.

Key Results and Discussion

Thermal Response and Stability

The gravity-driven radiator demonstrated a "Goldilocks" response time. It is approximately 15.2 times faster than traditional floor heating while being only slightly slower than a standard air conditioner. During start-up (outdoor temperatures between -5.2°C and -1.0°C), the novel system raised indoor temperatures at 10.8°C/h, compared to 13.8°C/h for the AC and 1.3°C/h for floor heating.

Furthermore, the system provides superior thermal stability. By heating the room's envelope (surfaces), the room retains heat longer after shutdown, cooling at only 0.93°C/h compared to 1.97°C/h for the AC unit.

Optimization Findings

The integration of a low-speed fan significantly improved performance:

  • Fastest Warm-up: Achieved at a fan angle of 0° and air speed of 0.6 m/s.
  • Optimal Comfort: A fan angle of -45° and a speed of 0.4 m/s is recommended to balance temperature uniformity and draft risk.

Under these recommended settings, the system met "Class II" comfort standards based on Predicted Mean Vote (PMV) and Predicted Percentage of Dissatisfied (PPD) metrics.

Conclusion

This novel system successfully bridges the gap between fast-responding convective units and high-comfort radiant heating. While the current study used simplified CFD modeling and focused on alkyl dichloride, future research will explore more environmentally friendly working fluids and specific control algorithms for long-term seasonal energy savings. The results confirm that a gravity-driven radiator coupled with an ASHP is a viable, responsive, and energy-efficient solution for intermittent heating in modern buildings.

Summary updated

Abstract

In this paper, a novel direct expansion air-source heat pump heating system with a gravity-driven radiator as a heating terminal was developed, for the purpose of reducing the energy consumption and improving the thermal comfort of indoor personnel. The thermal response speed of the system at the start-up stage was experimentally studied firstly. The results showed that the thermal response speed of the developed system was slightly lower than that of a traditional air-source heat pump heating system with a convective heating terminal, but largely higher than that of an air-source heat pump floor radiant heating system. When the outdoor air temperature fluctuated between −5.2 <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m1"><mml:mi mathvariant="italic">℃</mml:mi></mml:math> and −1.0 <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m2"><mml:mi mathvariant="italic">℃</mml:mi></mml:math> , the average rising ratios of indoor air temperature at the start-up stage for the developed heating system and the traditional system are 10.8 <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m3"><mml:mrow><mml:mi mathvariant="italic">℃</mml:mi><mml:mo>/</mml:mo><mml:mi>h</mml:mi></mml:mrow></mml:math> and 13.8 <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m4"><mml:mrow><mml:mi mathvariant="italic">℃</mml:mi><mml:mo>/</mml:mo><mml:mi>h</mml:mi></mml:mrow></mml:math> respectively. On this basis, an optimization study was then conducted to further improve the thermal performance of the developed heating system. The numerical results indicated that integrating a cross-flow fan to the gravity-driven radiator is able to promote the thermal performance of the heating system obviously at the start-up stage, because the convection heat transfer of the radiator was highly enhanced. Among the simulation conditions, the time required for the air temperature at head height to reach the designed temperature is shortest when the flow angle of the fan is 0 <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m5"><mml:mo>°</mml:mo></mml:math> with an air speed of 0.6 <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m6"><mml:mrow><mml:mi>m</mml:mi><mml:mo>/</mml:mo><mml:mi>s</mml:mi></mml:mrow></mml:math> . while setting the flow angle of the fan to −45 <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m7"><mml:mo>°</mml:mo></mml:math> with an air speed of 0.4 <mml:math xmlns:mml="http://www.w3.org/1998/Math/MathML" id="m8"><mml:mrow><mml:mi>m</mml:mi><mml:mo>/</mml:mo><mml:mi>s</mml:mi></mml:mrow></mml:math> is recommended to achieve the most thermal comfort for the whole body.
BibTeX
@inproceedings{wang2022experimental,
  author = {Haobo Wang and Yuanda Cheng and Dawei Wang and Weijin Peng and Zejian Ai and Jie Jia and Pengfei Duan and J.‐M. Yang},
  title = {{Experimental and Numerical Study on Thermal Performance of a Novel Direct Expansion Air-Source Heat Pump Heating System}},
  booktitle = {Frontiers in Energy Research},
  year = {2022},
  doi = {10.3389/fenrg.2021.765221},
}
Figure