MIMO Grid Impedance Identification of Three-Phase Power Systems: Parametric vs. Nonparametric Approaches

Verena Häberle, Linbin Huang, Xiuqiang He, Roy S. Smith, Florian Dörfler, Dörfler, Florian · DOI

Abstract

A fast and accurate grid impedance measurement of three-phase power systems is crucial for online assessment of power system stability and adaptive control of grid-connected converters. Existing grid impedance measurement approaches typically rely on pointwise sinusoidal injections or sequential wideband perturbations to identify a nonparametric grid impedance curve via fast Fourier computations in the frequency domain. This is not only time-consuming, but also inaccurate during time-varying grid conditions, while on top of that, the identified nonparametric model cannot be immediately used for stability analysis or control design. To tackle these problems, we propose to use parametric system identification techniques (e.g., prediction error or subspace methods) to obtain a parametric impedance model directly from time-domain current and voltage data. Our approach relies on injecting wideband excitation signals in the converter's controller and allows to accurately identify the grid impedance in closed loop within one injection and measurement cycle. Even though the underlying parametric system identification techniques are well-studied in general, their utilization in a grid impedance identification setup poses specific challenges, is vastly underexplored, and has not gained adequate attention in urgent and timely power systems applications. To this end, we demonstrate in numerical experiments how the proposed parametric approach can accomplish a significant improvement compared to prevalent nonparametric methods.

Introduction

As global energy systems transition toward renewable sources, power grids are increasingly dominated by power electronics, specifically grid-connected converters. These devices interact with the utility grid in complex ways that can lead to power quality degradation or total system instability. To prevent such issues, engineers require precise knowledge of the grid impedance ($Z_g(s)$)—the relationship between voltage fluctuations and current changes at the Point of Common Coupling (PCC).

Traditionally, the "gold standard" for this measurement has been the frequency sweep method. However, this approach is inherently slow, often requiring several minutes to complete a single sweep, and can fail if grid conditions shift during the experiment. Furthermore, traditional nonparametric methods produce data points that are not immediately suitable for advanced control design or stability analysis.

Proposed Methodology

This paper proposes a parametric approach that identifies the grid's transfer function directly from time-domain data. Unlike nonparametric methods that generate a frequency-response curve, parametric identification yields a mathematical model (such as a state-space or transfer function model) that is immediately ready for stability analysis (e.g., Nyquist criterion) or adaptive control tuning.

1. Wideband Excitation

Instead of injecting single-frequency sinusoids, the proposed method utilizes low-level wideband signals, such as Pseudo-Random Binary Sequences (PRBS) or Random Binary Signals (RBS). These signals are injected directly into the existing converter's $dq$-current control loop, eliminating the need for specialized external hardware.

Control block diagram of the grid-connected converter with wideband excitation injection.

2. Data Processing and Identification

Voltage ($v$) and current ($i$) measurements at the PCC are transformed into the $dq$ (direct-quadrature) frame. This transformation converts AC signals into DC-like quantities, simplifying the identification of Multi-Input Multi-Output (MIMO) systems. The study employs two primary identification techniques:

  • Prediction Error Methods (PEM): Used to fit an Auto-Regressive with Exogenous Variables (ARX) model.
  • Subspace Methods (n4sid): Used to identify a state-space model directly.

Comparative Analysis of Approaches

The core advantage of the parametric approach lies in its efficiency and the utility of its output. While nonparametric methods provide a "cloud of points" in the frequency domain, parametric methods provide a structured model that captures critical cross-coupling terms ($Z_{dq}$ and $Z_{qd}$) often ignored by simpler techniques.

Comparison of nonparametric and parametric grid impedance identification methods.

As shown in the comparison above, parametric methods offer a "one-shot" identification cycle that is computationally fast and highly accurate, even in the presence of switching noise from the converter's IGBTs. By selecting a higher model order (e.g., a 16th-order model for a 10th-order system), the algorithms can effectively "soak up" discretization errors and noise, resulting in a cleaner fit of the underlying grid physics.

Experimental Results

The parametric approach was validated through high-fidelity numerical experiments in MATLAB/Simulink using a 1.5 kVA three-phase system. The results demonstrate significant improvements over traditional methods:

  • Speed: The parametric method required only 15 seconds of data collection, a massive improvement over the 400 seconds required for a standard frequency sweep.
  • Accuracy: The ARX parametric model achieved an average magnitude error of -33.6 dB, outperforming both the frequency sweep (-31.7 dB) and sequential nonparametric wideband methods (-24.2 dB).
  • Efficiency: High accuracy was achieved using significantly fewer data points and lower total injection energy, minimizing the impact on grid operation.

Conclusion and Future Work

Parametric system identification offers a transformative path for real-time grid monitoring. By providing accurate MIMO models in a fraction of the time required by traditional sweeps, this method enables more robust stability assessments in weak grids. Future research will focus on automating model order selection (e.g., using the Akaike Information Criterion) and implementing these algorithms on embedded microcontrollers for autonomous, on-board grid impedance identification in commercial converters.

Summary updated

Abstract

A fast and accurate grid impedance measurement of three-phase power systems is crucial for online assessment of power system stability and adaptive control of grid-connected converters. Existing grid impedance measurement approaches typically rely on pointwise sinusoidal injections or sequential wideband perturbations to identify a nonparametric grid impedance curve via fast Fourier computations in the frequency domain. This is not only time-consuming, but also inaccurate during time-varying grid conditions, while on top of that, the identified nonparametric model cannot be immediately used for stability analysis or control design. To tackle these problems, we propose to use parametric system identification techniques (e.g., prediction error or subspace methods) to obtain a parametric impedance model directly from time-domain current and voltage data. Our approach relies on injecting wideband excitation signals in the converter's controller and allows to accurately identify the grid impedance in closed loop within one injection and measurement cycle. Even though the underlying parametric system identification techniques are well-studied in general, their utilization in a grid impedance identification setup poses specific challenges, is vastly underexplored, and has not gained adequate attention in urgent and timely power systems applications. To this end, we demonstrate in numerical experiments how the proposed parametric approach can accomplish a significant improvement compared to prevalent nonparametric methods.