Ultrafast Grid Impedance Identification in dq-Asymmetric Three-Phase Power Systems

Mohamed Abdalmoaty, Verena Häberle, Xiuqiang He, Florian DörflerarXiv 2025 · DOI · arXiv

Introduction

As the global energy landscape shifts toward renewable sources and electric vehicle infrastructure, power grids are becoming increasingly "converter-heavy." This transition introduces significant dynamic complexity, making real-time monitoring of grid stability essential. A critical parameter for ensuring this stability is the grid impedance ($Z_g(s)$), which characterizes how the grid responds to fluctuations in voltage and current.

Traditional methods for identifying grid impedance often struggle with speed or accuracy. Passive methods rely on existing grid noise, which is often insufficient for a full-spectrum analysis. Active methods, while more robust, typically require specialized hardware or long measurement periods to reach a steady state. Furthermore, many existing approaches oversimplify the grid as being perfectly symmetric, ignoring the dq-asymmetry (differences between direct and quadrature axes) common in modern power systems.

Proposed Methodology

To address these challenges, researchers have developed an active, non-parametric frequency-domain identification method designed for speed and precision. The approach leverages three key technical innovations:

  1. Complex Transfer Functions: By representing the grid using complex variables ($v = G_+i + G_-i^*$), the researchers can elegantly model asymmetric systems and simplify the mathematics of multi-input multi-output (MIMO) dynamics.
  2. Local Parametric Modeling: To overcome "spectral leakage" caused by non-periodic data, the method fits low-order "local" AutoRegressive with eXogenous terms (ARX) models to small frequency windows. This allows for accurate impedance estimation even from short, transient data bursts.
  3. Converter-Based Excitation: Instead of requiring external signal generators, the method utilizes the existing grid-connected inverter. A Random Binary Signal (RBS) is injected directly into the control loop, enabling "ultrafast" identification in less than one second.
Control diagram showing the injection of the excitation signal into the VSC current control loop.

Simulation and Validation

The effectiveness of the proposed method was validated through detailed electromagnetic transient (EMT) simulations in MATLAB/Simulink. The test environment featured a 10th-order asymmetric grid model with multiple resonances and line impedances, connected to a simulated 1.5 kVA voltage-sourced converter (VSC) operating at a 10 kHz switching frequency.

The study compared the new "local" modeling approach against standard global ARX models and traditional sequential perturbation methods to benchmark its performance in both noise-free and realistic industrial environments.

Key Results and Insights

The proposed method demonstrated significant improvements over existing techniques in three main areas:

  • Speed and Resolution: Identification was achieved in under one second, a drastic reduction compared to traditional frequency sweeps that can take minutes. Despite this speed, the method successfully captured sharp resonance peaks with a 3dB-bandwidth of only 5 Hz.
  • Accuracy under Noise: In noise-free scenarios, the method achieved a 100% fit across the 0–4 kHz range. Even with 0.5% measurement noise—typical for industrial sensors—it maintained a >98% fit for all impedance components.
  • Handling Asymmetry: The results highlighted that assuming symmetry ($Z_{dd} = Z_{qq}$) leads to significant errors. The complex-variable approach accurately captured the distinct behaviors of the $d$ and $q$ axes, which is vital for reliable stability analysis.
Magnitude plots of the identified grid impedance components, showing complex resonance peaks.

Conclusion

This research provides a robust framework for real-time grid monitoring in modern power systems. By combining local parametric modeling with existing converter hardware, the method offers a high-resolution "fingerprint" of grid impedance without the need for specialized equipment or long wait times. Future work will focus on experimental validation in laboratory settings and exploring the method's performance in "weak" grids where multiple converters may interact.

Summary updated

BibTeX
@misc{abdalmoaty2025ultrafast,
  author = {Mohamed Abdalmoaty and Verena Häberle and Xiuqiang He and Florian Dörfler},
  title = {{Ultrafast Grid Impedance Identification in dq-Asymmetric Three-Phase Power Systems}},
  year = {2025},
  eprint = {2510.12338},
  archivePrefix = {arXiv},
  url = {https://arxiv.org/abs/2510.12338},
}
Figure