Abstract
Energy storage in data centers has mainly been used as devices to backup generators during power outages. Recently, there has been a growing interest in using energy storage devices to actively shape power consumption in data centers to reduce their skyrocketing electricity bills. In this paper, we consider using energy storage in data centers for two applications in a joint fashion: reducing peak demand charges and enabling data centers to participate in regulation markets. We develop an optimization framework that captures the cost of electricity, degradation of energy storage devices, as well as the benefit from regulation markets. Under this framework, using real data Microsoft data center traces and PJM regulation signals, we show the electricity bill of a data center can be reduced by up to 20%. Furthermore, we demonstrate that the saving from joint optimization can be even larger than the sum of individually optimizing each component. We quantify the particular aspects of data center load profiles that lead to this superlinear gain. Compared to prior works that consider using energy storage devices for each single application alone, our results suggest that energy storage in data centers can have much larger impacts than previously thought possible.
Introduction
Data centers are power-hungry giants, with electricity bills often reaching millions of dollars annually. These bills typically consist of two parts: the total energy consumed and a "peak demand charge" based on the highest amount of power drawn at any single moment. To avoid these charges, data centers can use on-site batteries to "shave" the peaks. Additionally, emerging "regulation markets" pay large consumers to adjust their power usage in real-time to help the grid balance supply and demand.
The challenge is that data center batteries are designed for short-term backup; they have high power capacity but low energy capacity. This makes them poor at shaving long, "flat" peaks because they run out of juice before the peak ends. Previous research treated peak shaving and regulation as separate tasks. This paper asks: can we do both at once, and does the synergy between these tasks solve the energy-capacity limitation?
Methods
The authors develop a convex optimization framework that captures three competing factors: electricity costs (minimizing energy usage and peak draw), regulation revenue (maximizing fees from the PJM regulation market), and battery health (accounting for lithium-ion degradation).
The core novelty lies in the joint optimization. Instead of dedicating a slice of the battery to each task, the framework allows the battery to switch fluidly between them. To understand why this works, the authors also introduce a Peak Abstraction Model, categorizing power spikes by height, width, and shape. This model helps explain how the high-power capability of data center batteries can be fully utilized to overcome their low-energy limitation.
Key Insights: The "Superlinear" Gain
The most striking finding is that $1 + 1 > 2$. The savings from joint optimization are greater than the sum of doing peak shaving and regulation separately. This synergy exists because regulation signals are zero-mean and highly volatile. When a data center faces a long, flat peak that would normally drain a battery, the "randomness" of the regulation signal creates tiny valleys. These valleys allow the battery to briefly recharge or pause its discharge, effectively "breaking" one long, impossible peak into several smaller, manageable ones.
Furthermore, the authors found that 90% of real data center peaks are "narrow" (lasting less than 2 minutes) and "triangular." This specific profile is perfectly suited for battery intervention, allowing for efficient peak shaving even with limited energy capacity.
Results and Impact
Using real Microsoft traces and PJM signals, the joint strategy reduced total electricity costs by up to 30%. In a simulation of over 4,400 hours, the "superlinear gain" occurred in 93.4% of the hours.
As shown in the comparison above, joint optimization (c) maintains a more dynamic battery state-of-charge compared to single-purpose strategies, leading to the lowest normalized electricity bill (d). On average, joint optimization provided an extra 6.5% in savings beyond what could be achieved by simply adding the results of two separate optimization programs.
Conclusion
This research demonstrates that energy storage in data centers can have much larger impacts than previously thought. By moving beyond simple backup roles and embracing joint optimization for grid services and peak management, data center operators can achieve significant cost savings while contributing to grid stability. Future work will focus on moving from offline optimization to real-time online controllers that can handle the inherent unpredictability of power demand and regulation signals.
Summary updated