Abstract
With the enhancement of people's awareness of environmental protection and the improvement of environmental quality requirements, it is necessary to evaluate the effect of kitchen smoke exhaust on the environment. We introduced the structural definition of the parameters involved in the centralized exhaust flue and the range hood model in the centralized flue exhaust system. The iterative function calculation flow of the smoke output is clarified and the convergence of the iterative function was verified. To ensure the accuracy of parameters in the control equation which include the combined resistance coefficient of the pipeline's inner wall, we used CFD to solve resistance coefficients in the flue model of this smoke exhaust system. This solution was later verified experimentally. We deployed C# language for parametric programming, which allowed us to accommodate changes in different conditions. These include the number or height of layers, flue size, hood model, branch pipe length and type, valve angle, check valve type, and operating rate, among others. The results show that different pipe structures and smoke exhaust conditions are represented as a whole by parameters, which can be quickly calculated and displayed visually visualization program of flow changes in various layers inside the centralized exhaust flue. Lastly, we utilized the model to simulate a scenario, following which we evaluated the impact of the centralized exhaust flue in that scenario. The results of this study can guide the modeling of centralized flue systems and the evaluation of the effect of the exhaust pipe.
Introduction
In modern high-rise residential buildings, kitchen ventilation relies on a complex network of shared pipes. Smoke from individual range hoods travels through branch pipes and check valves into a massive centralized flue. However, existing models for these systems often rely on oversimplified fixed resistance values, failing to account for the dynamic "traffic jams" that occur when multiple residents cook simultaneously. This often results in poor air quality and "smoke backflow" for residents on lower floors. This study presents a high-fidelity parametric simulation tool designed to accurately predict pressure and flow changes across every floor of a building.
Methodology
The researchers developed a multi-stage approach to bridge the gap between theoretical physics and practical engineering:
- Mathematical Modeling: Governing equations were established based on the standard $k$-$\epsilon$ turbulence model for steady incompressible flow.
- CFD Simulations: Detailed simulations of specific components—including branch pipes, tee-junctions, and check valves—were performed using Fluent and Gambit to calculate precise resistance coefficients.
- Parametric Programming: These findings were implemented into a C# program. This allows for rapid calculation of flow changes based on variables such as floor count, flue size, valve angles, and hood models, bypassing the need for computationally expensive 3D simulations for every new scenario.
- Experimental Validation: Physical test benches and a real-world 33-layer vertical flue (the Vanke Tower) were utilized to verify the digital model's accuracy.
Key Insights and Results
The study revealed significant "exhaust inequality" within high-rise structures. In a 100% startup scenario (where all residents are cooking), a top-floor resident might achieve an exhaust rate of 648 $m^3/h$, while a ground-floor neighbor may struggle with only 185 $m^3/h$.
Key findings include:
- Resistance Coefficients: The comprehensive resistance coefficient of a standard branch pipe was determined to be 2.76.
- Check Valve Sensitivity: Resistance is highly sensitive to the opening angle but relatively independent of air volume. This relationship is described by the exponential formula: $\xi = k_1 e^{k_2(90-\theta)}$.
- Operating Rate Impact: Reducing the startup rate from 100% to 69.7% nearly doubled the exhaust volume for bottom-floor users (from 185 $m^3/h$ to 314 $m^3/h$), leading to a more uniform system performance.
Conclusion
The developed parametric model provides a fast and accurate method for evaluating centralized exhaust systems. To mitigate exhaust inequality, the study suggests that developers consider high-performance range hoods specifically for lower-floor residents to overcome the high static pressure in the central flue. Future work will focus on incorporating dynamic factors such as oil accumulation and variable surface roughness to further refine the model's real-world applicability.
Summary updated