Accuracy and Application Scope Analysis for Linearized Branch Flow Model in Radial Distribution Systems

Hanyang Lin, Xinwei Shen, Qinglai Guo, Hongbin Sun

Abstract

An in-depth analysis of linearized branch flow (LBF) model considering current injection and absolute value of impedance is proposed in this paper. The form of LBF model is based on two equations: the current injection to meet KCL and the voltage drop to meet KVL. By representing the absolute value of complex load power with the current injection, LBF model is much simpler than alternating current power flow (ACPF) model. The results on theoretical analysis and numerical studies show that LBF exhibits the high accuracy in bus voltage magnitude but a poor performance in branch flow. Moreover, LBF is also compared with fast decoupled linearized power flow (FDLPF) model to verify its efficiency, thus proving its superiority for fast evaluation of large-scale distribution systems with high accuracy in voltage magnitude. Finally, this paper analyzes three factors to lower LBF's errors of branch flow, as well as LBF's possible application scope.

Introduction

In modern power systems, calculating voltages and currents across a network—the "power flow" problem—is essential for managing renewable energy integration and grid reconfiguration. While Alternating Current Power Flow (ACPF) is the gold standard for accuracy, its nonlinear and non-convex nature makes it computationally expensive for large-scale optimization. Traditional shortcuts like DC Power Flow (DCPF) are unsuitable for distribution networks due to high resistance-to-reactance ($r/x$) ratios and non-negligible voltage drops. This paper evaluates the Linearized Branch Flow (LBF) model as a high-speed, linear alternative specifically designed for radial distribution systems.

Methodology

The LBF model analyzed in this study is derived from two fundamental physics principles: Kirchhoff’s Current Law (KCL), where current injection is represented by the absolute value of complex load power, and Kirchhoff’s Voltage Law (KVL), where voltage drop is calculated using the absolute value of branch impedance and current.

Radial branch flow model structure used for distribution system analysis.

The performance of LBF was benchmarked against ACPF (solved via Second-Order Cone Programming as the ground truth) and the Fast Decoupled Linearized Power Flow (FDLPF) model. These were tested across standard radial distribution systems, including 33-bus, 69-bus, and 141-bus configurations. To investigate grid safety margins, a Modified LBF (MLBF) model was also introduced using a scaling coefficient ($a = 1.08$) to provide conservative bounds for branch flows.

Key Results and Discussion

The study reveals a significant trade-off between speed, voltage accuracy, and branch flow precision. LBF emerged as the most computationally efficient model; in the 141-bus test, it solved in 5.69 seconds, compared to 16.84 seconds for FDLPF and 78.16 seconds for the AC model.

Voltage Accuracy vs. Branch Flow

A critical finding is that LBF's voltage magnitude accuracy improves relative to FDLPF as the system size increases. For the 141-bus system, LBF achieved an average voltage magnitude error of approximately 0.43%, significantly outperforming FDLPF's 1.5% error. However, this comes at the cost of branch flow precision, where LBF's error was higher (5.16%) compared to FDLPF (2.74%).

Error analysis for the 141-bus system comparing voltage magnitude and branch flow accuracy.

Bounding and Application Scope

Mathematical proofs within the paper demonstrate that LBF inherently underestimates node voltages. In grid planning, this provides a "conservative" lower bound, ensuring that if the LBF model predicts acceptable voltages, the actual system state is likely even safer. Furthermore, the MLBF variant successfully produced consistent upper bounds for branch flows, which is vital for preventing line overloads during planning phases.

Conclusion

While LBF's branch flow accuracy may be insufficient for high-precision applications like protection relay settings, its speed and superior voltage accuracy in large-scale systems make it an ideal tool for Distribution System Expansion Planning (DSEP) and network reconfiguration. The model is particularly effective as a "warm-start" mechanism—providing a fast initial guess to accelerate more complex, non-linear optimization algorithms in smart grid management.

Summary updated

Abstract

An in-depth analysis of linearized branch flow (LBF) model considering current injection and absolute value of impedance is proposed in this paper. The form of LBF model is based on two equations: the current injection to meet KCL and the voltage drop to meet KVL. By representing the absolute value of complex load power with the current injection, LBF model is much simpler than alternating current power flow (ACPF) model. The results on theoretical analysis and numerical studies show that LBF exhibits the high accuracy in bus voltage magnitude but a poor performance in branch flow. Moreover, LBF is also compared with fast decoupled linearized power flow (FDLPF) model to verify its efficiency, thus proving its superiority for fast evaluation of large-scale distribution systems with high accuracy in voltage magnitude. Finally, this paper analyzes three factors to lower LBF's errors of branch flow, as well as LBF's possible application scope.
BibTeX
@inproceedings{lin2021accuracy,
  author = {Hanyang Lin and Xinwei Shen and Qinglai Guo and Hongbin Sun},
  title = {{Accuracy and Application Scope Analysis for Linearized Branch Flow Model in Radial Distribution Systems}},
  booktitle = {2021},
  year = {2021},
  doi = {10.1109/pesgm46819.2021.9637880},
}
Figure