Abstract
Traditional DC power flow models, while computationally efficient, often suffer from significant inaccuracies due to assumptions of losslessness and flat voltage profiles. This paper introduces enhanced linear power flow models that incorporate linearized line losses and a convex approximation of apparent power. These modifications bridge the gap between the speed of DC models and the accuracy of full AC models, providing a robust framework for large-scale power system optimization.
Introduction
In power systems engineering, the AC Power Flow model is considered the "Gold Standard" for accuracy. However, its non-linear and non-convex nature makes it computationally prohibitive for large-scale optimization problems like market clearing or disaster recovery. To maintain efficiency, the industry typically relies on the DC Power Flow model. While fast, the DC model makes three critical assumptions: it assumes lines are lossless, bus voltages are flat (1.0 p.u.), and it ignores reactive power. These simplifications can lead to significant errors in line loading calculations, potentially resulting in mispriced energy or cascading blackouts.
Methodology
The authors propose three primary modifications to the standard DC model to enhance its fidelity without sacrificing the efficiency of a Linear Programming (LP) framework:
- Linearized Line Losses: The researchers introduce a piecewise linear approximation of quadratic line losses. By using two non-negative variables per line and a system of inequalities, they form a convex hull of the quadratic loss function, effectively capturing heat loss during transmission.
- Voltage Magnitude Integration: In "hot-start" scenarios where a previous AC solution is available, the model replaces the standard 1.0 p.u. assumption with actual voltage magnitudes. This adjustment significantly improves the accuracy of bus phase angle calculations.
- Convex Apparent Power Approximation: Instead of solving for complex reactive power, the authors model apparent power ($S$) directly as a convex function of phase angles. Using a collection of linear inequalities, they approximate the $S = \sqrt{P^2 + Q^2}$ relationship, allowing the model to accurately identify line overloads.
Experimental Evaluation
The proposed models were evaluated using seven standard power system benchmarks, including IEEE 14, 30, 57, and 118 bus systems, as well as the large-scale IEEEdd17 benchmark. These cases represent a range of network sizes and complexities where traditional DC models often struggle.
Results and Discussion
The study found that line losses are the primary contributor to inaccuracies in active power flow. By addressing these losses, the model achieved a 10x improvement in accuracy for the IEEEdd17 benchmark, reducing the worst-case absolute error from 200 MW to just 21 MW.
As illustrated in the correlation plots above, the linearized models track the full AC flow with high precision across multiple metrics. The apparent power approximation is particularly noteworthy; while the traditional DC model consistently underestimates line loading, the new convex approximation eliminates major outliers and tends toward a slight overestimation, providing a safer margin for grid operators who must adhere to strict thermal limits.
Conclusion
By integrating linearized losses and convex approximations of apparent power, this research provides a pathway to high-fidelity power system modeling within a computationally efficient linear framework. Future work will focus on refining phase angle residuals and extending the model to distributed slack bus configurations to better reflect real-world grid balancing.
Summary updated