Thermal Characterization of a Tier0 Datacenter Room in Normal and Thermal Emergency Conditions

Mohsen Seyedkazemi Ardebili, Carlo Cavazzoni, Luca Benini, Andrea Bartolini

Abstract

Datacenters are at the heart of the AI, Industry 4.0 and cloud revolution. A datacenter contains a large number of computing nodes hosted in a large temperature-controlled room. Due to the increasing total power and power density of computing nodes, the overall datacenter compute capacity is often capped by peak power consumption and temperature bottlenecks. To preserve the homogeneous performance assumption between all the nodes, complex cooling solution are required, but they might not be sufficient. In this work, we analysed and characterised the thermal properties of a Tier0 datacenter deploying advanced hybrid cooling technologies: specifically, we studied the spatial and temporal heterogeneity during production and cooling emergency hazards. This paper gives first quantitative evidence of thermal bottlenecks in real-life production workload, showing the presence of significant spatial thermal heterogeneity which could be exploited by thermal-aware job scheduling and datacenter-room run-time workload adaptation and distribution.
BibTeX
@inproceedings{ardebili2019thermal,
  author = {Mohsen Seyedkazemi Ardebili and Carlo Cavazzoni and Luca Benini and Andrea Bartolini},
  title = {{Thermal Characterization of a Tier0 Datacenter Room in Normal and Thermal Emergency Conditions}},
  booktitle = {HPCSE},
  year = {2019},
  doi = {10.1007/978-3-030-67077-1\_1},
}