This paper investigates the accumulation of surface charge on Resin Impregnated Paper (RIP) wall bushings under high-voltage DC conditions, a critical failure point in HVDC systems. By combining theoretical modeling with experimental measurements, the study reveals that surface charge primarily accumulates at a specific radius point, potentially compromising insulation, and provides insights for improved bushing design.

What Problem Does This Paper Address?

High-voltage direct current (HVDC) transmission systems rely on components like Resin Impregnated Paper (RIP) wall bushings to connect different voltage levels. However, these bushings are known weak points, particularly concerning surface charge accumulation under DC voltage. This phenomenon can lead to reduced insulation performance and, in severe cases, catastrophic failures like flashovers. Unlike AC systems where electric fields are governed by permittivity, DC fields are heavily influenced by conductivity, making surface charge accumulation a more complex and critical issue. Existing research has primarily focused on other insulator types, leaving a gap in understanding the specific surface charge behavior in RIP wall bushings, which feature a unique electric field equalizing structure. This paper aims to fill that gap by studying the surface charge accumulation characteristics of a model RIP wall bushing core under positive DC voltage.

Methods

The researchers employed a two-pronged approach: theoretical simulation and experimental measurement.

Theoretical Modeling: * Model: A scaled RIP wall bushing core was designed using the equal capacitance method. The simulation focused on the indoor section of the bushing, assuming rotational symmetry. * Gas Model: A gas model was developed to simulate the stationary resistive field along the gas-solid interface. This model incorporates a non-linearly field-dependent volume conductivity for the SF6 gas surrounding the bushing. * Ion Dynamics: The model accounts for the generation, recombination, migration, and diffusion of positive and negative ions in the SF6 gas, using established equations for ion pair generation rate, diffusion coefficients, and mobility ratios. * Surface Charge Model: A model for surface charge density on the RIP core was established, considering normal current density from both the core and gas sides, tangential electric field, and surface conductivity. * Boundary Conditions: Appropriate Dirichlet and floating boundary conditions were defined for electric potential and charge carrier densities to solve the governing differential equations.

Experimental Measurement: * Surface Charge Measurement System: An electrostatic probe method was utilized. This system comprises a central inductive probe, an outer shielding, a PTFE insulation support, and a BNC connector for signal transmission to a charge amplifier (Kistler 5018 A). * Experimental Setup: The experiment involved applying positive DC voltage to the RIP wall bushing core within a gas-insulated substation (GIS) bushing and transfer unit. The setup was filled with SF6 gas at 0.3 MPa. * Procedure: The RIP core was meticulously cleaned and dried. After ensuring no residual charge, DC voltage was applied for specific durations. Surface charge measurements were taken using the probe at a fixed distance of 2 mm from the core surface. The probe scanned the surface along an axial direction. * Data Analysis: The charge decay time constant was determined, and surface charge distribution patterns were analyzed under varying voltage amplitudes and durations.

Datasets

Not discussed in the paper. The study utilizes a self-designed model RIP wall bushing core and experimental data generated from this setup.

Key Insights and Ideas

  • Arched Gas Conductivity: The gas conductivity along the RIP wall bushing core surface exhibits an "arched" distribution, being highest in the middle and lower at the ends, from the high-voltage conductor towards the end shielding screen. This non-uniformity is crucial for understanding charge distribution.
  • Charge Accumulation Hotspot: Surface charge, particularly positive charge under positive DC voltage, predominantly accumulates at the "turning point of the radius" of the bushing core. This localized accumulation creates a potential weak point for insulation.
  • Time Constant Significance: The surface charge decay time constant is found to be around 15 minutes. This implies that measurements taken too soon after voltage application might not reflect the steady-state condition, and measuring the entire circumference might be impractical due to charge dissipation.
  • Shielding Effect: The end shielding screen plays a role in reducing surface charge accumulation in its vicinity, likely due to its electric field equalizing function.
  • Simulation-Experiment Consistency: The experimental results for surface charge distribution closely align with the simulation outcomes, validating the developed model.

Key Results

  • Ion Distribution: Positive and negative ion distributions in the SF6 gas are opposite and largely independent of the applied voltage amplitude within the tested range. Positive ions concentrate near the end shielding screen, while negative ions are near the high-voltage conductor.
  • Surface Charge Accumulation: Under positive DC voltage, the RIP wall bushing core surface accumulates positive charge. This accumulation saturates within approximately 15-20 minutes.
  • Charge Decay: Surface charge density decreases exponentially over time, with a decay time constant of about 15 minutes.
  • Electric Field Peaks: The tangential electric field is minimal at the radius turning point and maximal near the end shielding screen. Conversely, the normal electric field shows a peak at the radius turning point, correlating with the surface charge accumulation and indicating a potential insulation weak spot.
  • Model Validation: Experimental measurements of surface charge distribution were found to be highly consistent with simulation results.

Limitations and Future Work

Limitations: * Model Simplification: The simulation models the indoor section of the bushing and assumes rotational symmetry, which might not capture all real-world complexities of the entire bushing. * Material Properties: While the study uses a specific RIP material, variations in material properties could influence surface charge behavior. * Experimental Conditions: The experiments were conducted under controlled laboratory conditions (specific temperature, humidity, SF6 pressure). Real-world operating conditions might differ.

Future Work: * Shielding Measures: The authors suggest that shielding methods, such as adding a shielding ring at the front part of the high-voltage conductor, should be investigated to mitigate the electric field and surface charge concentration at the radius turning point. * Negative DC Voltage: The study focused on positive DC voltage. Investigating surface charge accumulation under negative DC voltage would provide a more complete picture. * Combined Stresses: Future research could explore the combined effects of DC voltage with other stresses like thermal or mechanical loads on surface charge accumulation and insulation performance. * Long-Term Behavior: While charge decay was studied, long-term aging effects on surface charge accumulation and insulation integrity could be a valuable area for further investigation.

Summary updated

Abstract

As a critical component of a high-voltage direct current (HVDC) transmission system, resin impregnated paper (RIP) wall bushing has become a weak point because of its surface charge accumulation. This paper studies a model RIP wall bushing core designed by the equal capacitance method. The stationary resistive field along the gas–solid interface of the RIP wall bushing core is investigated theoretically by a gas model, which considers the non-linearly field-dependent volume conductivity. The results show that the gas conductivity along the core surface tends to be an arched distribution from the high-voltage conductor to the end shielding screen. The surface charge mainly accumulates at the turning point of the radius, which may threaten the core’s insulation. Then, the surface charge is obtained through a measurement system, where the experimental results are highly consistent with the simulation results. Considering the time constant of charge dissipation is nearly 15 min, it would be better to measure the surface charge on one axial direction of RIP wall bushing core after each voltage application. The simulation and experimental results of this paper can guide the design of a RIP wall bushing core.