Simulation analysis of distance protection maloperation caused by sympathetic inrush current in transformer

Jigang Xu, Yi Mei, Gang‐Ding Peng, Yao Zhou, Xia JingJournal of Physics Conference Series 2025

Abstract

Abstract After the successful startup of the #2 main transformer at the 110kV Ruixia Substation under no-load conditions, the no-load closing of the #1 main transformer caused an incorrect operation of the distance protection, affecting four protection zones. Through theoretical analysis, it was determined that this issue resulted from the sympathetic inrush current. Additionally, a detailed PSCAD electromagnetic transient simulation model was created to further simulate and verify the event. Based on these simulations, a practical and feasible solution was proposed. This paper presents both theoretical and simulation-based analysis of an actual grid event, offering valuable insights for analyzing similar incidents and preventing their recurrence.