Abstract
The improvement of the automation level in electricity-heat integrated energy systems (IESs) has laid the foundation for load transfer after contingencies. As the energy coupling core and energy supply source, the energy hub (EH) plays an important role in IESs, where the load of EH's pipeline segment outlets is defined as operating points. This paper proposes a security region (SR) model considering EH equipment and pipeline segment N-1 contingencies alongside normal operation. Based on the security boundary of the SR, the distance from an operating point to a boundary is presented for security assessment. The effectiveness of the proposed SR model and assessment method is demonstrated on a test case, providing actionable guidance for system dispatchers.
Introduction
As cities transition toward Integrated Energy Systems (IES)—where electricity, gas, and heat are managed in a coordinated fashion—ensuring reliability becomes significantly more complex. Traditionally, operators have relied on "point-wise" security assessments, checking specific operating states individually to verify safety. However, this approach is computationally slow and fails to provide a "big picture" view of how much load can increase before the system becomes vulnerable.
The challenge is particularly acute in electricity-heat systems because the two sectors are coupled via Energy Hubs (EHs). These hubs contain equipment like Combined Heat and Power (CHP) units and electric boilers that create interdependencies between the power grid and the thermal network. This paper defines a "Security Region" (SR)—the entire set of operating points where the system remains safe even if one component fails—specifically for these coupled networks.
Methodology: The Energy Hub and Security Region
The authors utilize the Energy Hub (EH) concept to model the interface between the electrical grid and the district heating network.
The approach involves three main steps:
- Defining Operating Points: The system's state is defined based on the load at the outlets of the Energy Hub’s pipeline segments.
- Constructing the Security Region (SR): The SR is the set of all operating points satisfying both normal operating conditions and N-1 security (surviving the failure of any single piece of equipment or pipeline segment). This region is bounded by linear inequalities, forming a hyper-polyhedron in multi-dimensional space.
- Security Distance Calculation: To make the model actionable, the authors calculate the "distance" from the current operating point to the nearest security boundary. A positive distance means the system is secure; a negative distance indicates it is insecure.
Case Study and Key Results
The model was evaluated using a customized test case representing a typical urban electricity-heat IES, including two Energy Hubs and 14 pipeline segments (defining a 14-dimensional operating space). The analysis identified 28 distinct security boundaries (hyper-planes) that define the safe operating envelope.
Quantifiable Assessment
- Light Load (Point A): In this scenario, all distances to boundaries were positive, confirming N-1 security. The smallest margin (0.15 MW) was related to the electric boiler load, identifying it as the system's current "weakest link."
- Heavy Load (Point B): In this scenario, the system was found to be insecure, with negative distances to six different boundaries.
As shown in the results for Point B, the negative distances provide a clear roadmap for dispatchers: they must reduce the load on specific segments to return the system to the Security Region.
Conclusion and Future Work
The shift from checking individual points to defining a "region" allows for near-instantaneous security assessment once boundaries are calculated. By treating security as a distance in N-dimensional space, dispatchers receive a clear "buffer" value, knowing exactly how much more load can be added safely.
While this model provides a robust framework, the authors acknowledge simplifications regarding pipeline transmission capacity and linearization. Future work will aim to develop more accurate SR models that account for complex fluid dynamics in heat pipes and voltage stability in the power grid, alongside automated optimization methods to steer insecure points back into the safe region.
Summary updated