Abstract
To solve the problem that the voltage and current of power consumption in key areas of urban distribution networks exceed the safe range of power consumption, research on power consumption security in key areas of urban distribution networks is carried out. Under the condition of the feeder N-1 criterion, the maximum power supply capacity model of the urban distribution network is established. The theory of feeder interconnection is introduced to determine the security region of the distribution network. The security response is carried out for power users in key areas, and a new power security scheme is proposed. The example proves that the application of the safety guarantee scheme can control the voltage and current in the key areas of urban distribution networks within a safe range, and improve the overall operation safety of urban distribution networks.
Introduction
As cities grow more dependent on stable electricity, the stakes for power outages rise from mere inconveniences to significant threats to public safety and economic stability. Traditional urban distribution networks often lack the sophisticated emergency response mechanisms needed to handle sudden faults.
The core challenge is maintaining "power security" in key urban areas—ensuring that even if a piece of equipment fails (the N-1 scenario), the remaining network can pick up the slack without pushing voltage or current levels into dangerous territory. The authors identify a gap in current systems where voltage and current frequently exceed safe operating ranges during stress, leading to equipment damage or cascading failures.
Methodology
The researchers developed a multi-stage approach to define and maintain a "safe zone" for the grid:
- Maximum Power Supply Capacity (TSC) Modeling: They established a mathematical model to calculate the absolute limit of power a network can deliver while still satisfying the N-1 criterion. This criterion dictates that the system must remain functional if any single feeder or transformer fails.
- Feeder Interconnection & Security Regions: To handle the computational complexity of large networks, the authors introduced matrix operations to represent the state of all feeders. They defined a Security Region ($\Omega$)—a high-dimensional mathematical space where all operating points are guaranteed to be safe.
- Security Response Function: The paper introduces a demand-side management component. When a fault occurs, the system calculates a required "power reduction" ($Q_p$) for specific user groups to transition the network from a compromised state back into the defined Security Region.
Case Study and Results
The paper utilizes a simulated model of a city distribution network. The case study features a network structure with four main nodes (S12 and S22 transformers, each 40MVA) and multiple interconnected feeders. The model uses standard urban operating targets: a nominal voltage of 220V and a target current of 63.4A.
The authors tested their scheme against a baseline where no security measures were applied. The results show a dramatic improvement in stability:
- Voltage Stabilization: Before the scheme, voltages in various groups fluctuated wildly between 203.2V and 235.2V. After applying the security scheme, all five test groups stabilized almost perfectly between 220.0V and 220.3V (well within the ±5% safety target).
- Current Optimization: Initial current levels were inconsistent (51.2A to 60.2A). The proposed scheme brought these levels much closer to the optimal design target, ranging from 63.1A to 63.8A.
Conclusion
The proposed security framework demonstrates that by defining a pre-calculated "envelope" of safety, grid security can be mathematically guaranteed. One of the key innovations is the shift from raw linear programming to matrix operations, allowing for real-time response. While the current model assumes an "ideal environment" regarding power flow dynamics, future iterations will integrate real-world constraints such as impedance and reactive power losses to further refine the boundaries of the Security Region.
Summary updated