Research on the Application of Uncertainty Quantification (UQ) Method in High-Voltage (HV) Cable Fault Location

Bin Yang, Zhanran Xia, Xinyun Gao, Jing Tu, Hao Zhou, Jun Wu, Mingzhen LiEnergies 2022

TL;DR

This paper investigates the impact of uncertainty in high-voltage (HV) cable parameters on fault location accuracy. It compares three uncertainty quantification (UQ) methods – Monte Carlo Simulation (MCS), Polynomial Chaos Expansion (PCE), and Univariate Dimension Reduction Method (UDRM) – demonstrating their effectiveness and highlighting UDRM's potential for practical HV fault location due to its high convergence rate and accuracy.

What Problem Does This Paper Address?

Accurately locating faults in high-voltage (HV) power cables is crucial for grid reliability. However, the electrical parameters of these cables (like sheath resistivity, grounding resistance, and length) are not perfectly known and can vary due to factors like aging, environmental conditions, and maintenance practices. These uncertainties can significantly affect the accuracy of fault location algorithms, leading to misidentification of the fault point. Existing fault location methods often assume precise parameter values, neglecting this inherent uncertainty. This paper aims to quantify the impact of these parameter uncertainties on fault location and evaluate different UQ methods for their ability to model and mitigate these effects.

Methods

The study employs an impedance-based fault location criterion and investigates the impact of three key uncertain parameters: sheath resistivity per unit length, equivalent grounding resistance on both sides, and cable section length. These parameters are modeled with a 50% amplitude variation under a uniform random distribution.

Three UQ methods are compared:

  • Monte Carlo Simulation (MCS): A straightforward method that involves running numerous simulations with randomly sampled input parameters to estimate the output distribution. It's often used as a benchmark but can be computationally expensive due to its slow convergence rate (1/√N).
  • Polynomial Chaos Expansion (PCE): This method represents the model's output as a series of orthogonal polynomials. It offers high precision and fast convergence but can become computationally complex for highly nonlinear problems or a large number of uncertain inputs.
  • Univariate Dimension Reduction Method (UDRM): This technique decomposes the original function into a sum of single-variable functions. It aims to achieve a good balance between accuracy and computational efficiency, with a focus on faster convergence and more concentrated output distributions.

The paper analyzes the statistical properties (mean, standard deviation, coefficient of variation, mean absolute percentage error) and running times of these methods under various uncertainty scenarios.

Datasets

The study uses a simulated HV cable model based on parameters from a typical cross-connected HV cable system. The structural parameters of the cable are provided in Table 1, and the simulation scenario involves a 110 kV three-phase voltage source, a balanced load, and a short-circuit fault in a specific cable section (A1). No real-world datasets were used for training or evaluation; instead, a detailed simulation model was constructed.

Key Insights and Ideas

  • UQ is essential for HV fault location: The paper strongly advocates for the necessity of UQ in HV cable fault location, demonstrating that parameter uncertainties significantly influence the results.
  • UDRM shows promise for practical application: UDRM stands out due to its significantly higher mean convergence rate and more concentrated output distributions compared to MCS, making it a strong candidate for real-time HV fault location.
  • Different uncertainties have varying impacts: The study observed that changes in sheath resistivity tend to "flatten" the waveform of the calculated results, while changes in cable length lead to more spread-out waveforms. Grounding resistance uncertainties resulted in relatively concentrated distributions.
  • Trade-offs exist: While PCE offers high accuracy, its computational cost can increase significantly with complexity. MCS is simple but computationally intensive. UDRM appears to strike a good balance.

Key Results

  • Effectiveness of UQ: All three UQ methods (MCS, PCE, UDRM) were found to be effective in simulating fault location under uncertainty.
  • Close quantification results: The statistical quantification results (mean values) from MCS, PCE, and UDRM were generally very close across different scenarios.
  • UDRM's convergence advantage: UDRM exhibited a significantly higher mean convergence rate than MCS.
  • Accuracy and speed: PCE and UDRM demonstrated higher accuracy compared to MCS. Both PCE and UDRM required less running time than MCS, with UDRM being particularly efficient.
  • Specific performance: For example, in Table 3 (sheath resistivity under normal operation), UDRM achieved a Cvar of 0.3247 and a Mape of 0.2891 with a running time of 0.438s, while MCS had a Cvar of 0.3386 and Mape of 0.2975 but took only 0.133s. However, PCE methods (PCE_2, PCE_3, PCE_4) showed lower Cvar and Mape values (e.g., 0.1346 and 0.1023 for PCE_2) but had longer running times (around 0.554s).

Limitations and Future Work

  • Experimental validation: The paper acknowledges that actual experiments and applications of these UQ methods on HV cables are still in their early stages.
  • Practical parameter settings: Determining realistic uncertainty ranges and verification methods for practical fault scenarios remains a challenge.
  • Cost-effectiveness: The maximum number of tests and cost considerations for implementing these methods in real-world applications need further study.
  • Future research: The authors suggest that future work should focus on addressing these practical limitations, including experimental validation and cost-benefit analysis.

Summary updated

Abstract

In HV cable fault location technology, line parameter uncertainty has an impact on the location criterion and affects the fault location result. Therefore, it is of great significance to study the uncertainty quantification of line parameters. In this paper, an impedance-based fault location criterion was used for an uncertainty study. Three kinds of uncertainty factors, namely the sheath resistivity per unit length, the equivalent grounding resistance on both sides, and the length of the cable section, were taken as random input variables without interaction. They were subject to random uniform distribution within a 50% amplitude variation. The relevant statistical information, such as the mean value, standard deviation and probability distribution, of the normal operation and fault state were calculated using the Monte Carlo simulation (MCS) method, the polynomial chaos expansion (PCE) method, and the univariate dimension reduction method (UDRM), respectively. Thus, the influence of uncertain factors on fault location was analyzed, and the calculation results of the three uncertainty quantification methods compared. The results indicate that: (1) UQ methods are effective for simulation analysis of fault locations, and UDRM has certain application prospects for HV fault location in practice; (2) the quantification results of the MCS, PCE, and UDRM were very close, while the mean convergence rate was significantly higher for the UDRM; (3) compared with the MCS, PCE, and UDRM, the PCE and UDRM had higher accuracy, and MCS and UDRM required less running time.
BibTeX
@inproceedings{yang2022research,
  author = {Bin Yang and Zhanran Xia and Xinyun Gao and Jing Tu and Hao Zhou and Jun Wu and Mingzhen Li},
  title = {{Research on the Application of Uncertainty Quantification (UQ) Method in High-Voltage (HV) Cable Fault Location}},
  booktitle = {Energies},
  year = {2022},
  doi = {10.3390/en15228447},
}
Figure