NeurIPS 2026Coming to NeurIPS?Explore papers, orals & directions

Real-Time Cooling Power Attribution for Co-Located Data Center Rooms with Distinct Temperatures

Yonggang Wen, Rongrong Wang, Duc Van Le, Rui Tan, Yew-Wah Wong, Yonggang Wen 0001

Abstract

At present, a co-location data center often applies an identical and low temperature setpoint for its all server rooms. Although increasing the temperature setpoint is a rule-of-thumb approach to reducing the cooling energy usage, the tenants may have different mentalities and technical constraints in accepting higher temperature setpoints. Thus, supporting distinct temperature setpoints is desirable for a co-location data center in pursuing higher energy efficiency. This support calls for a new cooling power attribution scheme to address the inter-room heat transfers that can be up to 9% of server load as shown in our real experiments. This paper describes our approaches to estimating the inter-room heat transfers, using the estimates to rectify the metered power usages of the rooms' air handling units, and fairly attributing the power usage of the shared cooling infrastructure (i.e., chiller and cooling tower) to server rooms by following the Shapley value principle. Extensive numeric experiments based on a widely accepted cooling system model are conducted to evaluate the effectiveness of the proposed cooling power attribution scheme.
BibTeX
@inproceedings{wen2020real,
  author = {Yonggang Wen and Rongrong Wang and Duc Van Le and Rui Tan and Yew-Wah Wong and Yonggang Wen},
  title = {{Real-Time Cooling Power Attribution for Co-Located Data Center Rooms with Distinct Temperatures}},
  booktitle = {Buildsys},
  year = {2020},
  doi = {10.1145/3408308.3427607},
}

Loading related content...

Figure