Optimal Dispatch of Photovoltaic Inverters in Residential Distribution\n Systems

Emiliano Dall’Anese, Sairaj V. Dhople, Georgios B. Giannakis

Abstract

Low-voltage distribution feeders were designed to sustain unidirectional power flows to residential neighborhoods. The increased penetration of roof-top photovoltaic (PV) systems has highlighted pressing needs to address power quality and reliability concerns, especially when PV generation exceeds the household demand. A systematic method for determining the active- and reactive-power set points for PV inverters in residential systems is proposed in this paper, with the objective of optimizing the operation of the distribution feeder and ensuring voltage regulation. Binary PV-inverter selection variables and nonlinear power-flow relations render the novel optimal inverter dispatch problem nonconvex and NP-hard. Nevertheless, sparsity-promoting regularization approaches and semidefinite relaxation techniques are leveraged to obtain a computationally feasible convex reformulation. The merits of the proposed approach are demonstrated using real-world PV-generation and load-profile data for an illustrative low-voltage residential distribution system.

Introduction

Residential power grids were originally designed for unidirectional power flow from substations to homes. However, the rapid adoption of rooftop photovoltaic (PV) systems has introduced bidirectional flows. When solar generation significantly exceeds local demand, it can cause "overvoltages"—voltage levels exceeding safe limits—which risk damaging grid equipment or triggering inverter shutdowns.

Existing solutions typically rely on local control strategies: Reactive Power Control (RPC), where inverters absorb or inject reactive power, and Active Power Curtailment (APC), where solar energy is simply discarded. These local methods often fail to coordinate, leading to system-wide inefficiencies such as high line losses or excessive curtailment at the end of a feeder while other inverters remain idle.

Methodology

This paper proposes a unified "Optimal Inverter Dispatch" (OID) framework that treats the neighborhood as a coordinated system. The problem is formulated as an Optimal Power Flow (OPF) task, which is traditionally difficult due to the non-convexity of power flow equations and the combinatorial complexity of selecting which inverters to control.

To address these hurdles, the authors employ two key mathematical techniques:

  1. Sparsity-Promoting Regularization (Group-Lasso): This identifies a small, critical subset of inverters to manage the grid, avoiding the need to micromanage every household.
  2. Semidefinite Relaxation (SDR): This transforms non-convex equations into a convex Semidefinite Program (SDP), allowing for global solutions to be found in less than a second.

The framework was validated using a standard low-voltage radial feeder model (Figure 1) with real-world load data from Saint Paul, MN, and PV profiles from NREL’s System Advisor Model.

Figure 1: Schematic of the residential distribution system used for validation, featuring 12 houses (H1-H12) connected to a central feeder.

Key Results and Discussion

The OID strategy demonstrates superior performance in maintaining voltage stability and system efficiency. By jointly optimizing active ($P$) and reactive ($Q$) power, the system achieves a much "flatter" voltage profile across the feeder compared to uncoordinated methods (Figure 3).

Figure 3: Voltage magnitude profiles across the feeder nodes. The OID strategies (red lines) successfully keep voltages within the required 0.917–1.042 pu range, whereas the "No OID" case (black) exceeds limits.

Key quantitative findings include:

  • Efficiency Gains: Daily energy losses were reduced to 14.2 kWh with OID, compared to 83.7 kWh for standard APC.
  • Economic Impact: Coordinated dispatch is significantly more cost-effective over a full year by minimizing wasted solar generation and line losses.
  • Computational Speed: The algorithm solves in approximately 0.27 seconds, making it feasible for real-time grid implementation.

Conclusion

Coordinated inverter dispatch offers a robust solution for managing high PV penetration in residential areas. While the current model assumes perfect communication and single-phase balance, it provides a foundation for future work addressing forecast uncertainties and three-phase system imbalances. The results prove that a system-wide optimization approach is essential for the efficiency and reliability of modern distribution grids.

Summary updated

Abstract

Low-voltage distribution feeders were designed to sustain unidirectional\npower flows to residential neighborhoods. The increased penetration of roof-top\nphotovoltaic (PV) systems has highlighted pressing needs to address power\nquality and reliability concerns, especially when PV generation exceeds the\nhousehold demand. A systematic method for determining the active- and\nreactive-power set points for PV inverters in residential systems is proposed\nin this paper, with the objective of optimizing the operation of the\ndistribution feeder and ensuring voltage regulation. Binary PV-inverter\nselection variables and nonlinear power-flow relations render the novel optimal\ninverter dispatch problem nonconvex and NP-hard. Nevertheless,\nsparsity-promoting regularization approaches and semidefinite relaxation\ntechniques are leveraged to obtain a computationally feasible convex\nreformulation. The merits of the proposed approach are demonstrated using\nreal-world PV-generation and load-profile data for an illustrative low-voltage\nresidential distribution system.\n
BibTeX
@article{dallanese2014optimal,
  author = {Emiliano Dall’Anese and Sairaj V. Dhople and Georgios B. Giannakis},
  title = {{Optimal Dispatch of Photovoltaic Inverters in Residential Distribution\textbackslash\{\}n Systems}},
  journal = {IEEE Transactions on Sustainable Energy},
  year = {2014},
  doi = {10.1109/tste.2013.2292828},
}
Figure