Introduction
As electronic components continue to shrink while power densities increase, thermal management has become a critical bottleneck in engineering design. Traditional thermal management systems (TMS) typically employ "single-split" architectures, where a single coolant source distributes fluid to various components through parallel branches. While straightforward to design, these architectures often prove sub-optimal for complex layouts containing localized "hot spots."
The transition to "multi-split" systems—where fluid can branch at any point—offers significant performance advantages but introduces immense design complexity. The number of possible configurations grows exponentially with the number of components, making manual design impractical. This paper presents an automated framework that combines spatial clustering, graph-based physics modeling, and optimal control to identify the most efficient cooling layouts for high-density electronics.
Automated Design Framework
The proposed pipeline automates the transition from physical component layout to an optimized cooling system. The process begins with Spatial Clustering, using K-means on the physical coordinates of heat-generating devices to identify logical locations for fluid junctions. These layouts are then represented as acyclic undirected graphs, with the coolant tank as the root and Cold Plate Heat Exchangers (CPHXs) as nodes.
Physics Modeling and Optimization
A key innovation of this framework is the Automated Physics Modeling step. The system automatically converts graph representations into dynamic state-space equations. These models account for three primary heat transfer mechanisms: advection (fluid moving heat), convection (heat moving from wall to fluid), and bi-directional advection at the heat exchanger interface.
For every generated architecture, the framework solves an Optimal Open Loop Control (OLOC) problem. This optimization determines the ideal flow rates for each valve to maximize "thermal endurance"—the total operational time before any component reaches its critical temperature safety limit.
Key Insights and Results
The research demonstrates that multi-split architectures consistently outperform traditional single-split designs. By allowing branching closer to heat sources, the system can deliver cooler fluid to high-load components more effectively.
Experimental results from a 3-node case study with asymmetric loads (12kW vs. 1kW) showed that a multi-split configuration achieved a thermal endurance of 69.9 seconds, significantly better than standard series or parallel layouts. Furthermore, the "best" architecture was found to be load-dependent; optimal graphs typically place high-heat components closer to the pump to ensure maximum cooling capacity.
An interesting observation from the optimal control results is that the system sometimes restricts flow to certain branches initially. This strategy preserves cooling capacity, ensuring all components reach their temperature limits simultaneously, thereby maximizing total system runtime.
Conclusion and Future Work
The framework successfully scales to complex systems, as demonstrated by an 18-node case study. While current methods rely on enumerating possible graphs—which may be limited for extremely large systems—future work will explore Genetic Algorithms or Machine Learning to navigate the design space more efficiently. Additionally, the researchers aim to incorporate more sophisticated hydraulic models and 3D pipe routing constraints to further bridge the gap between automated design and physical implementation.
Summary updated