Modelling on Bus-Transfer Current and Enclosure Current of GIS

Feng Xue, Yida Sheng, Haitao Li, Chaoming Wang, Siwei Wan, Siwei Ma2015 · DOI

Abstract

As the continuous development of social economy, a large number of gas insulated switchgear (GIS) has been put into use for its advantages. In order to prevent disconnector faults during the process of substation switching operation, it's important to measure the bus-transfer current to monitor the running status of disconnectors. By analyzing the structure of GIS, this paper proposes a method to figure out the relationship between the enclosure current and the bulk current of GIS. The work of theoretical study in this paper is helpful in measuring the bus-transfer current to discover the potential risks of substation switching operation in advance. It not only greatly improves the operation and motion reliability of gas insulated switchgear devices, but also brings high power supply reliability and huge economic benefit to our society.

Introduction

Gas Insulated Switchgear (GIS) has become a cornerstone of modern power infrastructure due to its compact footprint and high reliability. However, the disconnectors within these systems are subject to mechanical and electrical stresses during switching operations. A common failure mode involves poor electrical contact, which can lead to overheating and catastrophic failure.

Monitoring the health of these internal components is challenging because the conductors are housed within pressurized, gas-filled metal tanks. Directly measuring the "bus-transfer current"—the current shifting between busbars—is technically difficult. This paper establishes a theoretical framework to non-invasively monitor GIS health by modeling the relationship between internal "bulk" currents and external enclosure currents, providing a diagnostic window into the system's status.

Methods of Modeling

The research approaches the problem through two distinct modeling stages designed to translate external measurements into internal diagnostics.

1. Bus-Transfer Current Modeling

The authors first treat the double-busbar setup as a parallel circuit. During switching operations, the current divides between two branches based on their respective line impedances (determined by physical length) and contact resistances. By using equivalent circuit diagrams, they can predict how the current should ideally distribute.

Equivalent circuit model for bus-transfer current distribution.

2. Enclosure Current Modeling

To relate the internal current to what can be measured externally, the authors conceptualize the GIS as a coreless transformer. In this model, the internal conductor acts as a single-turn primary winding, while the loop formed by the enclosure, its support brackets, and the ground acts as a single-turn secondary winding.

Physical model of the enclosure current loop in a GIS system.

Using the Biot-Savart law and magnetic flux equations, the authors derive formulas for mutual inductance ($M_{12}$) and leakage inductance ($L_{2s}$). This allows for a precise mathematical derivation of the relationship between the internal bulk current ($I_1$) and the induced enclosure current ($I_2$).

Key Insights and Results

The "Bad Contact" Signature

In a healthy GIS system, the current distribution is determined solely by the physical geometry and length of the busbar branches. However, when a disconnector develops a high-resistance "bad contact," the current distribution shifts dramatically. For instance, the study found that a contact resistance of just $2m\Omega$ could cause the proportion of current in a branch to drop from approximately 77% to 37%. This significant drop serves as a clear diagnostic signal for maintenance teams.

The 1:2 Rule of Thumb

A major practical takeaway from the electromagnetic derivation is that, under ideal conditions where enclosure-ground loop resistances are negligible, the enclosure current is approximately half of the internal bulk current ($I_2 \approx 0.5 \times I_1$). This relationship allows engineers to estimate internal loads using simple external current sensors.

Sensitivity to Faults

Numerical case studies validated the model's sensitivity. In one scenario, a fault caused the bus-transfer current proportion to drop from 90.9% to 63.4%. These results demonstrate that monitoring enclosure currents can effectively identify potential risks during substation switching operations before they manifest as hardware failures.

Limitations and Future Work

While the theoretical model provides a robust foundation, it relies on certain simplified assumptions. The conclusion that enclosure current is exactly half of the bulk current assumes that resistances in the enclosure-ground loop are small enough to be ignored—an assumption that may not hold for aged or poorly grounded systems. Additionally, while the paper addresses three-phase systems as ideally balanced, real-world imbalances may require more complex 3D electromagnetic modeling.

Future research will focus on translating these theoretical formulas into real-time hardware monitoring devices, further enhancing the reliability and economic efficiency of the power grid.

Summary updated

Abstract

As the continuous development of social economy, a large number of gas insulated switchgear (GIS) has been put into use for its advantages. In order to prevent disconnector faults during the process of substation switching operation, it's important to measure the bustransfer current to monitor the running status of disconnectors. By analyzing the structure of GIS, this paper proposes a method to figure out the relationship between the enclosure current and the bulk current of GIS. The work of theoretical study in this paper is helpful in measuring the bus-transfer current to discover the potential risks of substation switching operation in advance. It not only greatly improves the operation and motion reliability of gas insulated switchgear devices, but also brings high power supply reliability and huge economic benefit to our society.
BibTeX
@misc{xue2015modelling,
  author = {Feng Xue and Yida Sheng and Haitao Li and Chaoming Wang and Siwei Wan and Siwei Ma},
  title = {{Modelling on Bus-Transfer Current and Enclosure Current of GIS}},
  year = {2015},
  doi = {10.2991/ism3e-15.2015.64},
}
Figure