Mitigating the ferroresonance resulting from HILGF clearing in a remote area 10 kV power distribution network

Xueneng Su, Hua Zhang, Jing Wang, Zongmin Yu, Cheng LongThe Journal of Engineering 2025 · DOI

Abstract

Abstract To solve the problem of high impedance line‐to‐ground fault, a solution using isolation transformers for subnetwork divisions was previously implemented in the power distribution network. As a result of that, the network has been experiencing ferroresonance more often. Through modelling and simulation based on its actual parameters on the PSCAD/EMTDC, the understanding of the situation is deepened. The ferroresonance originates from the network response to the high impedance line‐to‐ground fault clearing. The subnetwork division has certainly improved the network fault damping factor, but the line capacitance reduction it caused has exposed the system to ferroresonance. To mitigate the ferroresonance, high‐frequency components are removed from the zero‐sequence current using the morphological filtering; then, through edge detection, it is used as the input signal to the control unit. The control unit then takes the ferroresonance mitigation action intelligently. The simulation results indicate that the proposed method can restore ferroresonance‐induced overvoltage and overcurrent to normal levels within 0.05 s.
BibTeX
@article{su2025mitigating,
  author = {Xueneng Su and Hua Zhang and Jing Wang and Zongmin Yu and Cheng Long},
  title = {{Mitigating the ferroresonance resulting from HILGF clearing in a remote area 10 kV power distribution network}},
  journal = {The Journal of Engineering},
  year = {2025},
  doi = {10.1049/tje2.70048},
}

Loading related content...

Figure