Abstract
In modern interconnected power systems, the failure of a single transmission line can trigger non-local surges, potentially leading to cascading failures across sub-grids. This paper proposes three specific "interface network" topologies—series, parallel, and complete bipartite—designed to connect sub-grids in a way that localizes failure impacts. Using the Line Outage Distribution Factor (LODF) as a metric, the authors prove that these strategic designs can isolate failures to a single sub-grid while maintaining the redundant connectivity necessary for overall grid reliability.
Introduction
Power systems are increasingly composed of interconnected sub-grids managed by diverse operators. While physical interconnection is necessary for power transfer and reliability, it introduces a vulnerability: the redistribution of power following a line trip often affects distant parts of the network. Grid designers face a fundamental tension between localization (minimizing inter-grid connections to stop cascades) and reliability (maximizing redundant paths). This research investigates whether it is possible to provably localize failures within sub-grids without creating single points of failure.
Methodology
The study utilizes the Line Outage Distribution Factor (LODF) to quantify the sensitivity of power flow on one line to a failure on another. The goal is to design interfaces that drive the LODF between lines in different sub-grids toward zero.
The authors propose three interface structures to connect two sub-grids via boundary buses $s$ and $t$:
- Series Interface: Increases topological distance by splitting boundary buses.
- Parallel Interface: Adds an auxiliary line to act as a local "pressure relief valve."
- Complete Bipartite Interface: A $2 \times 2$ structure that connects all four split-bus endpoints.
The theoretical framework is built on the linearized DC power flow model, with validation performed using the non-linear AC power flow model.
Key Insights
A central finding is the monotonicity of failure: the absolute value of the Power Transfer Distribution Factor (PTDF) increases with a line's susceptance. This allows for the "tuning" of line parameters to direct power flow away from sensitive sub-grids.
The complete bipartite network emerges as the most effective "network isolator." By selecting line susceptances that satisfy a specific "rank-1 condition" ($b_{ss'}b_{tt'} = b_{st'}b_{ts'}$), the failure impact on a neighboring sub-grid can theoretically be reduced to zero in a DC model. Importantly, these interfaces reduce cross-grid impacts without significantly altering the internal robustness of the sub-grid where the failure originated.
Results and Validation
The proposed topologies were evaluated using the IEEE 118-bus test network. Key results include:
- LODF Reduction: All three interfaces outperformed the original grid configuration in terms of failure localization.
- Bipartite Performance: In DC simulations, the bipartite interface reduced the frequency of high-impact line pairs (LODF > 0.01) from 10% to nearly zero.
- AC Robustness: While the "zero impact" result is theoretical for DC models, AC simulations confirmed substantial reductions in failure propagation under non-linear conditions.
- Connectivity: Unlike simple tree-partitioning, these interfaces maintain multiple paths, preventing sub-grids from "islanding" during a single line failure.
Conclusion
This research demonstrates that structural design can effectively mitigate cascading failures in power systems. Future work will address the challenges of scaling these $2 \times 2$ interfaces to larger, more complex connection points and integrating passive structural protections with active dynamic controls like automated load shedding.