Experimental Study on Solving Ice-blocking by Condensation Heat Recovery

Zhi Ming Han, Zhen Wang, Yaying Zhang, Tao Jiang, Hongli Shan2017 · DOI

Abstract: The problem of ice blockage has always been a thorny issue when the fluidized ice equipment is making ice. Based on the origin of ice blockage, we analyze the causes of the problem. And then, we melt the ice with hot water, that is: the heat carried from the compressor (this part of heat can transform 15.0 tap water into 55.0 high temperature hot water) is recycled, guaranteeing the temperature needed to melt ice. Finally, we carry out experiments of melting ice with hot water of different temperatures and find that the effect is better when the temperature is 55.0. Through the implementation of the above technical means, we've solved the ice-blocking when the fluidized ice equipment is making ice.

Introduction

In the fishery industry, "fluidized ice"—a slurry of seawater and ice crystals—is a superior refrigerant because it cools fish rapidly without damaging their delicate skin. However, the equipment used to make this ice frequently suffers from ice blockage. These blockages occur primarily due to physical resistance in narrow heat exchanger cylinders and the high surface energy of copper materials, which causes water molecules to easily adsorb and freeze onto the walls.

Traditional deicing methods, such as mechanical oscillation, are often inefficient. This study proposes a sustainable solution by recycling waste heat from the refrigeration cycle to produce hot water for deicing.

Methods

The proposed solution involves a Condensation Heat Recovery Unit integrated directly into the refrigeration cycle. In a standard cooling system, the compressor generates high-temperature, high-pressure gas (up to 96°C) that is typically exhausted as waste. This method intercepts that heat using a direct-sleeve-type heat exchanger.

Schematic of the integrated refrigeration and heat recovery system.

As shown in the system schematic, the hot refrigerant gas passes through a heat recovery heat exchanger before reaching the condenser. A cyclic heating system uses pumps to move water between a 200L storage tank and the heat exchanger, preventing thermal stratification and ensuring efficient heat transfer. This setup provides a reliable source of hot water to melt ice jams without requiring external energy inputs.

Key Results and Discussion

The experimental trials focused on two metrics: the heating efficiency of the recovery system and the effectiveness of the resulting hot water in clearing blockages.

Heating Efficiency

The system successfully utilized waste heat to raise the temperature of 200L of water. Experimental data indicates that the water temperature rose from approximately 20°C to over 50°C in roughly 115 minutes, aligning with the goal of reaching a 55°C target for optimal deicing.

Temperature rise of the 200L water tank over time.

Deicing Performance

Comparative trials were conducted at temperatures ranging from 40°C to 60°C. The researchers identified 55°C as the "sweet spot" for this configuration. At this temperature, a 1.5L ice blockage was completely melted in just 12 minutes.

Beyond solving the blockage problem, the researchers noted that the amount of condensation heat generated is roughly 1.3 times the actual refrigerating output. This represents a significant energy source that can also provide hot water for general domestic use at fishery facilities, further reducing the plant's overall carbon footprint.

Conclusion

By repurposing condensation heat, this study demonstrates a highly efficient method for solving ice blockages in fluidized ice equipment. The system not only clears jams rapidly using 55°C water but also improves the overall energy utilization of the refrigeration plant. Future work may explore the automation of this process through sensor-triggered deicing cycles and scaling the technology for industrial-sized operations.

Summary updated

Abstract

The problem of ice blockage has always been a thorny issue when the fluidized ice equipment is making ice. Based on the origin of ice blockage, we analyze the causes of the problem. And then, we melt the ice with hot water, that is: the heat carried from the compressor (this part of heat can transform 15.0 tap water into 55.0 high temperature hot water) is recycled, guaranteeing the temperature needed to melt ice. Finally, we carry out experiments of melting ice with hot water of different temperatures and find that the effect is better when the temperature is 55.0. Through the implementation of the above technical means, we've solved the ice-blocking when the fluidized ice equipment is making ice.
BibTeX
@misc{han2017experimental,
  author = {Zhi Ming Han and Zhen Wang and Yaying Zhang and Tao Jiang and Hongli Shan},
  title = {{Experimental Study on Solving Ice-blocking by Condensation Heat Recovery}},
  year = {2017},
  doi = {10.2991/icmia-17.2017.102},
}
Figure