Abstract
This paper presents an improved secondary voltage control (SVC) methodology incorporating compressive sensing (CS) for a multi-area power system. SVC minimizes the voltage deviation of the load buses while CS deals with the problem of the limited bandwidth capacity of the communication channel by reducing the size of massive data output from phasor measurement unit (PMU) based monitoring system. The proposed strategy further incorporates the application of a Morphological Median Filter (MMF) to reduce noise from the output of the PMUs. To keep the control area secure and protected locally, Mathematical Singular Entropy (MSE) based fault identification approach is utilized for fast discovery of faults in the control area. Simulation results with 27-bus and 486-bus power systems show that CS can reduce the data size up to 1/10th while the MSE based fault identification technique can accurately distinguish between fault and steady state conditions.
Introduction
As modern power grids integrate more distributed generation sources like solar and wind, maintaining voltage stability becomes increasingly challenging. Grids typically employ a hierarchical control structure where primary control acts locally on generators. However, to stabilize load buses across wider areas, Secondary Voltage Control (SVC) is required.
SVC relies on high-speed data streams from Phasor Measurement Units (PMUs), which introduces three major technical hurdles: data congestion in communication networks, sensor-induced signal noise, and the difficulty of distinguishing harmless noise from critical system faults. This paper proposes a unified framework that combines Compressive Sensing (CS), Morphological Median Filtering (MMF), and Mathematical Singular Entropy (MSE) to enable stable, real-time voltage regulation even under constrained communication bandwidth.
Methodology
The proposed framework integrates signal processing and control logic to ensure robust performance. The overall system architecture involves local data processing at the area level followed by centralized control action.
Secondary Voltage Control (SVC)
The SVC is formulated as an infinite norm minimization problem. Unlike traditional approaches that might average deviations, this method focuses on minimizing the worst-case voltage deviation across the control area, ensuring all buses remain within safe operating limits.
Compressive Sensing (CS) for Data Efficiency
To mitigate communication bottlenecks, the system leverages the inherent spatial and temporal correlations in power system data. Compressive Sensing allows PMU data to be encoded into a much smaller footprint before transmission. At the central controller, the Orthogonal Matching Pursuit (OMP) algorithm is used to reconstruct the original signal with high fidelity.
Local Intelligence: MMF and MSE
Before data is compressed and sent to the central controller, it undergoes local processing:
- Morphological Median Filter (MMF): This filter uses mathematical morphology (dilation and erosion) to smooth signals and remove noise while preserving the underlying shape of critical grid events.
- Mathematical Singular Entropy (MSE): By applying Singular Value Decomposition and Shannon Entropy to the filtered data, the system can detect faults locally. If entropy exceeds a specific threshold, local protection relays are triggered immediately, providing a safety net that operates independently of the central controller.
Experimental Results
The methodology was validated using simulated 27-bus and 486-bus power systems. The results highlighted several key advantages:
- Scalable Compression: The system achieved a 6:1 compression ratio for the 27-bus system and a 10:1 ratio for the 486-bus system. Larger grids exhibit higher spatial correlation, making CS even more effective as the system scales.
- Voltage Stability: The SVC algorithm successfully restored load bus voltages to their reference values (approximately 1.0 p.u.) within seconds following major load disturbances.
- Reliable Fault Detection: The MSE approach accurately distinguished between noise (entropy < 0.015) and actual faults (entropy > 0.08), allowing for a clear trigger threshold of 0.05.
- Reduced Latency: By reducing data volume by up to 90%, communication delays were significantly minimized, ensuring the real-time responsiveness of the secondary control loop.
Conclusion
This research demonstrates that integrating compressive sensing with local entropy-based fault detection provides a resilient solution for secondary voltage control in multi-area power systems. While the current implementation depends on the presence of at least one pilot bus per area, it effectively addresses the "big data" bottleneck of modern grid monitoring. Future work will explore more advanced, data-independent bases for CS to further enhance reconstruction accuracy in complex, volatile grid environments.