Analysis of the effect on propagation of voltage sag considering different winding connection modes of transformer

Jiming Chen, Lizhi Qi, Guiyue Jin, Yongduan Xue2016

Abstract

The propagation of voltage sags through transformers is significantly influenced by winding connection modes. This paper utilizes PSCAD simulation and mathematical transfer matrices to analyze how different configurations alter sag characteristics. Using the $Y_0/Y-12$ transformer as a primary case study, we examine propagation during single line-to-ground, line-to-line, and double line-to-ground faults. The resulting transfer laws provide critical insights for online monitoring, fault source location, and industrial mitigation strategies. Specifically, industrial plants can minimize sag-induced disruptions by optimizing transformer winding selections.

Introduction

Voltage sags—brief reductions in RMS voltage—represent a significant power quality challenge for modern industrial facilities. While often originating from faults on high-voltage transmission lines, the sags experienced at the low-voltage industrial bus are fundamentally altered by the intervening transformers. Transformers act as filters that modify the sag's amplitude, phase, and sequence components based on their winding configurations. Understanding these propagation laws is essential for accurate fault source location, equipment state evaluation, and the design of resilient power systems.

Methodology and Modeling

The research utilizes a dual approach combining theoretical mathematical derivation with high-fidelity simulation.

Mathematical Transfer Matrices

Voltage transfer matrices were derived for three common transformer configurations: $Y_0/Y_0-12$ (Star-Star, both points grounded), $Y_0/Y-12$ (Star-Star, secondary ungrounded), and $Y_0/\Delta-11$ (Star-Delta). A critical factor in these derivations is the handling of zero-sequence components. As shown in Figure 1, the physical connection determines whether zero-sequence currents can flow between the primary and secondary sides, which is the primary driver of sag transformation.

Equivalent zero-sequence circuits for different transformer winding connections.

Simulation Setup

Simulations were performed using PSCAD/EMTDC on a model representing a typical industrial supply chain. The primary transformer modeled was an SZ9-M-12500/35kV/6.3kV unit with a rated capacity of 12,500 kVA and 8% short-circuit impedance. Faults were introduced at 1.0s with a duration of 0.05s to observe the transient and steady-state sag characteristics across the transformer.

Analysis of Sag Propagation

The study reveals that transformer connections significantly influence how unbalanced faults propagate through the system, often redistributing the sag severity across phases.

The Zero-Sequence Barrier

The $Y_0/Y-12$ configuration serves as a notable example. Because the ungrounded secondary side blocks zero-sequence currents, the "shape" of the sag is redistributed. In the event of a single phase-to-ground fault on the primary side, the secondary side does not see a total collapse of one phase. Instead, the faulted phase typically drops to approximately 0.33 p.u., while the healthy phases experience a slight dip to roughly 0.88 p.u. This prevents a total interruption on any single phase.

Comparative Results

  • $Y_0/Y_0-12$: This configuration is essentially transparent to sags; the transfer matrix is a unit matrix, and the sag characteristics remain identical on both sides.
  • $Y_0/\Delta-11$: This connection is particularly robust for industrial applications. For most unbalanced sags, at least two phases remain above 0.58 p.u., which is often sufficient to prevent the tripping of sensitive electronic controllers.

Figure 2 illustrates the transformation of a single-phase fault through a $Y_0/Y-12$ transformer, highlighting the redistribution of voltage levels between the primary and secondary sides.

Comparison of voltage sag waveforms on the primary (a) and secondary (b) sides of a $Y_0/Y-12$ transformer.

Conclusion

The winding connection mode of a transformer is a decisive factor in the propagation of voltage sags. By strategically selecting connection modes, such as Star-Delta, industrial plants can mitigate the severity of sags and improve the ride-through capability of sensitive equipment. These findings provide a theoretical basis for utilities to implement more effective online monitoring and fault identification systems based on the sag signatures recorded at customer meters.

Future work should consider the impact of dynamic loads, such as large induction motors, which can provide voltage support during sags through back-EMF, potentially further modifying the propagation characteristics observed in this study.

Summary updated

Abstract

The effects of transformers on the types and characteristics of voltage sag are also different when the voltage sag is transmitted by the transformers, which have different winding connection modes. In this paper, using the system simulation model built by PSCAD, based on the derivation of voltage transfer matrix of transformers with different winding connection modes. Then, taking the Y0/Y-12 type transformer as an example analysed the propagation characteristics of voltage sag caused by single line-to-ground fault, line-to-line fault and double line-to-ground fault. The transfer law of voltage sag propagation of transformers with different winding connection modes is summarized. These laws provide some reference value with on line monitoring, type identification, source location of voltage sag and state evaluation. Industrial plants could reduce the harm caused by the voltage sag reasonable by the way of changing winding connection modes of transformer.
BibTeX
@misc{chen2016analysis,
  author = {Jiming Chen and Lizhi Qi and Guiyue Jin and Yongduan Xue},
  title = {{Analysis of the effect on propagation of voltage sag considering different winding connection modes of transformer}},
  year = {2016},
  doi = {10.2991/aest-16.2016.74},
}
Figure