Abstract
Three-phase unbalance control strategy is used to improve the system performance when three-phase unbalance load or fault happens. However, when the distributed generation selected as the master in the microgrid stop working, due to the loss of system voltage direction, the traditional control strategy is no longer applicable. In order to maintain the stable operation of the SST (Solid State Transformer) under passive microgrid model when three-phase unbalances occur in the microgrid, the paper came up a novel balance control strategy under passive microgrid model. The control strategy is based on the voltage and current double-loop control strategy, and uses a negative sequence current module to calculation the negative sequence reference current, prevent three-phase unbalance from entering into distribution grid side and improve the control performance of the SST. The simulation results have proved the validity and efficiency of the three-phase unbalance control strategy.
Introduction
In modern smart grids, the Solid State Transformer (SST) is a critical piece of hardware. Unlike traditional copper-and-iron transformers, SSTs use power electronics to provide better control over voltage and frequency. However, they face a significant challenge: three-phase unbalance. This happens when the load on one phase is much heavier than the others or when a fault occurs, leading to power quality issues.
Existing control strategies work well when a "master" distributed generator is providing a steady voltage reference to the microgrid. But what happens when that master generator stops working? The microgrid enters a "passive mode." In this state, traditional control methods fail because they lose their directional "anchor." The authors identify an "inner contradiction" in passive mode: you cannot simultaneously achieve perfectly balanced output voltage, constant frequency, and total isolation of the unbalance from the grid. This paper seeks a middle ground to keep the system stable during these critical transitions.
Methodology
The authors propose a control strategy based on a voltage and current double-loop architecture. The technical heavy lifting is done by a negative-sequence current calculation module.
Key steps in their approach include:
- Mathematical Modeling: Decomposing the three-phase system into positive-sequence and negative-sequence components using symmetrical component theory.
- Constraint Loosening: Recognizing that perfect balance is mathematically impossible in passive mode, they introduce tolerance parameters ($\epsilon_1, \epsilon_2$). This allows for a tiny, controlled amount of unbalance in the output voltage in exchange for much higher stability in active power.
- Negative-Sequence Reference: The system calculates a specific reference value for the negative-sequence current. This ensures that even if the local load is unbalanced, the SST compensates for it internally rather than letting the fluctuation destabilize the rest of the network.
The strategy was evaluated using a Matlab/Simulink simulation environment. The simulation parameters modeled a grid rated at 0.38kV with specific filter inductors (1.6mH), capacitors (3mF), and a DC side voltage of 0.7kV. A failure event was simulated at $t=0.5s$ to test the controller's response to sudden phase unbalance.
Key Insights and Results
The most significant insight is the formal identification of an "inner contradiction" in passive microgrids: three specific control targets (balanced voltage, constant amplitude/frequency, and preventing unbalance from entering the grid) are mutually exclusive. Instead of fighting for a perfect mathematical solution, the authors suggest that "loosening" the requirements for port voltage balance is the key to maintaining the consistency of active power.
The simulation results demonstrate the following:
- Active Power Stability: Under traditional control, active power showed significant oscillations during a three-phase unbalance. The proposed strategy successfully stabilized the active power, smoothing out the fluctuations.
- Voltage Performance: While the traditional method produced a slightly more "balanced" looking voltage waveform, it resulted in unstable power flow. The proposed method maintained a stable, albeit slightly less balanced, voltage that stayed within the defined tolerance levels.
- Grid Protection: The strategy effectively prevented the local unbalance from entering the distribution grid side, which is vital for preventing local microgrid issues from causing wider blackouts.
Conclusion
This paper presents a robust control strategy for SSTs operating in passive microgrids. By focusing on the negative-sequence current, the SST can act as a buffer, absorbing local unbalances and ensuring steady active power flow. While the simulation results are promising, future work should involve hardware-in-the-loop (HIL) testing to account for real-world factors like switching losses and sensor noise. Additionally, developing algorithms for dynamic adjustment of tolerance parameters could further enhance system resilience under complex fault scenarios.