Clothing as Slack: Comfort-Budgeted HVAC Control with a Latent Daily Insulation State

Office climate systems treat each occupant as a fixed thermostat target. People do not behave that way. On a cold morning someone arrives in a sweater and is comfortable at 20°C; the next day, in a shirt, they want 23°C. Field studies show this clothing flexibility is large: in winter homes in one Chinese climate zone, most occupants stay comfortable well below standard thresholds by dressing more warmly (Li et al.). The best-known energy result that relies on occupant feedback probably draws on the same flexibility. It lets indoor temperature drift toward outdoor conditions until someone complains, and it cut energy by 50–65% (Purdon et al.). That controller, however, never knows why people are tolerating the drift. It waits for a complaint to find out it has gone too far. In a shared office it stalls at the first complaint from the most sensitive or lightest-dressed person.

We propose a controller that tracks each occupant's clothing level today as an explicit hidden variable. That variable shifts the occupant's personal comfort temperature. The controller estimates it from a cheap one-tap clothing report ("lighter / usual / warmer than usual") instead of waiting for comfort complaints. It then picks per-zone temperature bands that save as much energy as possible while keeping the fraction of uncomfortable occupant-hours under a fixed budget. The claim is that clothing slack, once estimated per person and per day, is a more reliable source of energy savings than drift-until-complaint. It should also be safer than the fixed comfort envelopes used by current predictive controllers, and the advantage should be largest in shared zones where occupants differ.

Core Claim

Three bodies of work each hold one piece of this, and none holds the combination.

Personalized comfort models infer a stable personal comfort temperature and sensitivity from about ten votes. The Bayesian network of Auffenberg et al. reports a 23.5% accuracy gain over the standard heat-balance index (PMV) on ASHRAE RP-884. That model is offline and treats the comfort temperature as constant across days.

Controllers that include clothing treat it as a fixed input to a comfort predictor. DeepComfort feeds clothing insulation into a neural comfort model inside a continuous reinforcement-learning loop. Building simulations by Κόντες et al. show that setpoints fail unless they are adjusted for clothing. Neither estimates clothing online or exploits its day-to-day variation.

Predictive controllers can trade a stated comfort-violation budget for energy. DAD-DPC does this with conformal prediction, a distribution-free method for calibrated error bands. Its budget is defined against a fixed physical temperature band, so it cannot tell that today's band could be wider for a particular occupant.

Our model writes each occupant's expected thermal vote on the 7-point scale as

$$v_{i,d,t} = \gamma_i \left( T_{z(i),t} - T^*_i + \kappa\, c_{i,d} \right),$$

where the symbols are defined as follows:

  • $T_{z(i),t}$ is the operative temperature of occupant $i$'s zone at time $t$.
  • $T^*_i$ and $\gamma_i$ are the occupant's stable comfort temperature and sensitivity, as in Auffenberg et al.
  • $c_{i,d}$ is the occupant's clothing deviation on day $d$ from their usual level, measured in clo (the standard unit of clothing insulation).
  • $\kappa$ converts clo into an equivalent temperature shift. It is shared across people and fitted on RP-884, which records clo for every vote.

The controller maximizes energy savings subject to one constraint: the long-run fraction of occupant-hours with $|v| > 1$ stays below a budget $\alpha$. This mirrors how DAD-DPC exposes its violation budget, but the violation is now subjective and specific to each person and day. The new element is $c_{i,d}$. It is a fast, observable, day-level state. Knowing it before discomfort occurs tells the controller how much slack exists today.

Research Program

Decision timescale. The controller chooses a temperature-band offset for each zone for each half-day block. An existing low-level controller tracks that band: the BOPTEST baseline controller, or DAD-DPC itself. This choice deliberately addresses the gap between bandits and building dynamics that the research file flags. Fast thermal inertia is absorbed inside a block, so the reward for a block is approximately immediate. We will measure how much comfort and energy carry over between blocks. If the carryover is large, we will add the previous block's offset to the context rather than pretend the problem is memoryless.

Actions and learning. A joint action has two parts: an offset for every zone, plus an optional one-line morning clothing suggestion to each occupant. Across a floor, the number of joint actions grows multiplicatively.

What matters here is sample cost, not computation. An independent table of estimates per zone relearns every occupant from scratch. Our reward instead decomposes additively over occupants, with features built from the posterior over $(T^*_i, \gamma_i, c_{i,d})$ and an energy term that is approximately additive in zone offsets. This makes the reward linear in shared features. The best joint action is then a separable per-zone maximization, which is exactly the cheap linear optimization step that SpannerIGW needs. We reuse its exploration rule, which explores over a small representative set of actions and has regret bounds that grow with feature dimension rather than with the number of joint actions. The budget multiplier on discomfort is adapted online to hit $\alpha$.

The scalable-bandit machinery is a means to learn from few interactions. It is not the headline. The experiments below test whether it is needed at all.

Clothing inference. The daily clothing state gets a prior that depends on outdoor temperature and season, fitted to RP-884 clo distributions. The posterior is updated from the one-tap clothing report when one is given, and from comfort votes otherwise. Both kinds of tap count toward the same interaction budget of 4–6 per occupant per day, the level Purdon et al. found occupants tolerate.

A clothing tap should be worth more than a comfort vote for control. It reports slack before the occupant is uncomfortable, whereas a comfort vote typically arrives after the controller has already overshot. That is the specific mechanism we test.

Occupant simulator. No public testbed simulates dressing behavior, so we build one on top of the BOPTEST multi-zone office (DAD-DPC's Case 3). Simulated occupants are drawn from personalized models fitted per subject on RP-884. Their clothing follows the fitted weather-dependent model plus individual day-to-day noise. Their votes follow the equation above plus noise matched to RP-884's heavily neutral-skewed vote distribution. Their compliance with clothing suggestions is a swept parameter from zero upward, because the file contains no compliance data for clothing prompts. The acceptance dynamics reported for RECA's relocation prompts are the closest analogue and set our upper range.

We also validate the vote model on real data before any control experiment. On held-out RP-884 votes, we compare prediction when clo is observed, masked, or inferred from the prior plus one tap. This establishes whether $c_{i,d}$ carries signal beyond $T^*_i$. As a second check, we test on AutoTherm, which records clothing alongside votes. The reference points there are its LSTM at 59.3% 7-class accuracy and PMV at 35.9%.

Baselines

Fixed setpoint. The naive reference is the fixed 21.5–24.5°C band tracked by the default BOPTEST controller. All energy savings are reported relative to it.

Drift with voting. This reimplements Purdon et al.: 3-point votes shift the setpoint, and neutral periods let temperature drift toward ambient. For shared zones we use the paper's aggregation. It receives the same simulated occupants and the same vote budget. It is the most direct competitor because it exploits the same human slack without modeling it. Its reported field result is 50–65% energy savings with an average 0.3°C deviation from personal comfort zones. No reported result was found on Lacuna for drift on BOPTEST, so we measure it ourselves.

DAD-DPC. This is DAD-DPC with its fixed normative band, run at matched violation targets. It is the strongest published controller in the file. On BOPTEST Case 3 (multi-zone office) it reports 27.1% energy savings over the rule-based controller at a 5% violation target. We rerun it on the same weather and occupancy. Its violations are scored by our subjective-vote metric as well as its native physical one.

Personalized, clothing-blind. This baseline uses Auffenberg-style models with a constant comfort temperature and the same bandit and budget. It isolates the daily clothing state.

Discrete deep reinforcement learning. This is a RECA-style deep Q-network with the same state features. Following Wei et al., it is given the same number of simulated building-days, with tuning budgets matched in trials.

Ablations. We run the full method without suggestions, to separate exploiting natural clothing variation from prompting it. We also replace clothing taps with extra comfort votes at equal budget, to test the "slack before discomfort" mechanism.

Success criterion. Beating the baselines means lower energy than both drift and DAD-DPC at the same realized subjective violation rate, $\alpha \in \{2.5\%, 5\%, 10\%\}$, with no worse violation rate for the least-comfortable decile of occupants. The results must hold with suggestion compliance set to zero.

Why not just…?

Why not just use drift with voting, which already captures clothing implicitly? This is the real threat. If occupants dress warmly, drift keeps going until they object, and it may harvest most of the slack for free. Our hypothesis is that it loses in two places. First, it overshoots, because it learns the limit only through a complaint, which is costly under a violation budget. Second, in shared zones it stops at the first complaint regardless of who complained. The clothing-blind and equal-budget-vote ablations, run in single-occupant and shared zones separately, settle this. If drift matches us in single-occupant offices, we will report that the gain is confined to shared zones.

Why not just widen DAD-DPC's fixed band? A wider fixed band is the same for everyone and every day. On mild days, or for lightly dressed occupants, it pushes the subjective violation rate over budget. We will sweep DAD-DPC's band width and plot its energy-versus-subjective-violation curve against ours. If some fixed width lies on our curve, the per-day clothing state adds nothing and we will say so.

Why not just run independent learners per zone, or continuous deep reinforcement learning? Per-zone learners are computationally fine at office scale, so compute is not our argument. Their weakness is statistical: they cannot share what they learn about clothing response across occupants. We compare learning curves in simulated days to reach the budget. Continuous policy methods like DeepComfort cannot natively choose discrete per-person suggestions, and they needed 15,000 simulated hours. If per-zone learners reach the same final performance within a few weeks, we will drop the spanner component in favor of them.

Proposed Experiments

The first experiment is offline. On RP-884, we test whether the daily clothing term improves held-out vote prediction for the same person over Auffenberg's constant comfort temperature, and how much of that gain one clothing tap recovers. If inferred clothing adds nothing measurable, the control study is not worth running.

The second experiment is the closed-loop BOPTEST study. We run a full heating season and a shoulder season across three violation budgets, with ten occupant populations resampled from RP-884 subjects. We report energy, realized subjective violation rate, worst-decile violation rate, and taps per occupant per day, all against the baselines above.

The third experiment stress-tests the simulator assumptions, since conclusions about human behavior here rest on a simulator. We vary the day-to-day clothing variance, the conversion $\kappa$, vote noise, and suggestion compliance. We also add a fraction of occupants who bias their votes strategically, the failure mode raised by adversarially robust HVAC learning.

The decisive result would be a consistent energy reduction over both drift and DAD-DPC, at matched subjective violation rates, that holds with zero suggestion compliance. That would show the value comes from estimating clothing slack, not from persuading people to dress differently. If the gain appears only when compliance is high, the contribution shrinks to a nudging study, and we will present it that way.