Abstract
Low-voltage distribution grid (LVDG) topology detection refers to detecting whether the topology connection between distribution grid nodes is correct. Accurate topology connection is critical for the normal operation and planning of LVDG. However, due to the incomplete measurement device, unknown line parameters, and rapid growth of renewable energy, the topology detection of LVDG becomes one of the most prominent challenges. This paper proposes an LVDG topology detection method based on virtual impedance, utilizing measurement data from nodes in the LVDG to achieve the detection of abnormal topological connections. Specifically, the electrical distances between nodes are analyzed to establish a topology detection model using virtual impedance. Then, the double hidden layer recurrent neural network is proposed to fit the mapping relationships between variables in the power flow constraints. The virtual impedance between nodes is solved. The value of virtual impedance is used to determine whether the topological connection between nodes is correct. Finally, the test results in the actual LVDG prove the effectiveness of the proposed method.
Introduction
The "last mile" of the power grid—the low-voltage distribution grid (LVDG)—is becoming increasingly complex due to the rise of rooftop solar and electric vehicle charging. For utilities to manage this effectively, they need an accurate "map" (topology) of how nodes are connected. However, maintaining an accurate topology is notoriously difficult. Physical records are often outdated, line parameters (like resistance) are frequently unknown, and installing specialized sensors at every node is cost-prohibitive. Traditional data-driven methods often fail when faced with missing data or the non-linear complexities of power flow. This research seeks a way to "see" the grid's structure using only the data already being collected by smart meters, leveraging physics-informed machine learning to reconstruct power flow constraints.
Methodology
The proposed approach centers on the concept of Virtual Impedance, serving as a mathematical proxy for electrical distance. If two nodes are physically connected, their virtual impedance should be low; otherwise, it should exceed a specific threshold.
To solve for this virtual impedance, a Double Hidden Layer Recurrent Neural Network (DHLRNN) was developed. Recurrent networks are chosen for their ability to capture temporal dependencies in time-series power data. The double-layer structure allows the model to fit highly non-linear relationships between current, voltage, and power more accurately than standard single-layer architectures.
The DHLRNN fits the mapping between injected currents and active power. Once the virtual impedance is calculated and normalized, it is compared against a calculated threshold ($M_{th}$). If the value exceeds the threshold, the connection is flagged as abnormal.
Results and Discussion
The study validated its approach using real-world data from a practical LVDG in China, encompassing 6 low-voltage distribution transformers and 358 end-users. Data was collected over 24 hours at 15-minute intervals.
The DHLRNN method outperformed existing models across several metrics. The Mean Absolute Percentage Error ($e_{MAPE}$) for the DHLRNN was only 0.301%, significantly lower than standard RNN (0.562%) and CNN (0.926%) models. When compared against other popular methods like the MILP (Mixed-Integer Linear Programming) model and Graph Convolutional Networks, the proposed method consistently showed higher accuracy in identifying correct topological connections across all six tested transformer areas, often exceeding 98% accuracy.
The "aha moment" of this research is realizing that actual resistance measurements are unnecessary. By treating impedance as a learnable parameter (virtual impedance), the model bypasses the need for manual line audits.
Conclusion
This paper introduces a novel method for detecting wiring errors and topology changes in LVDGs without requiring expensive hardware installations. While the results are promising, challenges remain in extremely complex, mesh-like structures and sensitivity to data quality. Future work will focus on refining the algorithm for real-time applications, potentially allowing utilities to detect illegal connections or sudden line faults as they occur.
Summary updated