Transient Stability Analysis for Hybrid GFM-GFL Systems with Current Limit

Xiaonan Zhang, Ziyang Huang, Zihan Wang, Gengyin Li, Le Zheng, Shiwei Xia2024

Abstract

Due to the different grid-connection control, complex coupling between grid-following (GFL) inverter and gridforming (GFM) inverter significantly affects the transient stability of the hybrid GFM-GFL system. This paper establishes a hybrid GFM-GFL system model and focuses on the impact of GFM inverter current limit on the transient stability of the system. In addition, the interaction mechanism between GFL inverter and GFM inverter is revealed. The results indicate that the injected current of GFL inverter reduces the output power of GFM inverter, and once the current limit activities, the closer to π/2 for the power angle deviation between inverters of two types, the easier for their mutual synchronization. However, the system voltage is not controllable in this scenario, and the system transient stability weakens. Time-domain simulations have verified the theoretical analysis.
BibTeX
@misc{zhang2024transient,
  author = {Xiaonan Zhang and Ziyang Huang and Zihan Wang and Gengyin Li and Le Zheng and Shiwei Xia},
  title = {{Transient Stability Analysis for Hybrid GFM-GFL Systems with Current Limit}},
  year = {2024},
  doi = {10.1109/pesgm51994.2024.10688760},
}