Abstract
Accurate status analysis and reliable maintenance strategies are essential for the safe, reliable, and economic operation of power grids. This paper proposes a condition evaluation method for power transformer equipment based on multi-source information, including defects, testing results, and operational history. By establishing intelligent evaluation models and identification rules, the research provides a framework for optimizing maintenance plans throughout the equipment's service life, thereby enhancing grid safety and reliability.
Introduction
Power transformers serve as the critical infrastructure of the electrical grid. Given their high cost and essential role, ensuring their long-term reliability is paramount. Traditionally, utilities have relied on preventive maintenance—scheduled outages and manual inspections. However, this approach suffers from significant drawbacks, including information lag regarding real-time status, risks of maintenance-induced faults (estimated at 10% of failures), and economic inefficiency due to ignoring the actual health of individual units.
To address these issues, this research proposes an intelligent condition evaluation framework that integrates multi-source data to provide a data-driven maintenance roadmap.
Methodology
The proposed model utilizes a dual-layered approach: a weighted fault tree scoring system for initial state assessment and a Support Vector Machine (SVM) for precise fault classification.
Weighted Fault Tree Scoring System
The transformer is decomposed into four primary subsystems: General, Ontology (core and tank), Casing, and the Non-electricity Protection System. Each component is assigned a weight based on its criticality. Faults are categorized into levels with corresponding scores that determine the final state: Normal, Attention, Abnormal, or Severe.
A fundamental rule of this system is the "weakest link" principle: the overall evaluation follows the most serious condition found among any of the parts. This ensures that critical localized issues are not masked by the healthy state of other components.
Support Vector Machine (SVM) Classification
While traditional AI methods like Backpropagation (BP) neural networks have been applied to Dissolved Gas Analysis (DGA), they often require large datasets and can be slow to converge. In contrast, SVM is highly effective for "small sample" learning, which is typical for power grid failure data.
The researchers utilize an SVM with a Radial Basis Function (RBF) kernel to find the optimal hyperplane that separates different fault patterns. This approach offers superior generalization capabilities, allowing for accurate diagnosis even with limited historical failure data.
Data and Case Studies
The model was validated using operational data from the Yunnan Power Grid Corporation, including equipment from the 110kV Chajie, 110kV Huize, 220kV Fugong, and 35kV Dongshan substations.
Key findings from the case studies include:
- 110kV Huize Substation: The system identified serious seal aging and low oil levels in the #2 main transformer, recommending enhanced monitoring for the aging unit.
- 35kV Dongshan Substation: The model flagged specific fan motor damage on the #2 transformer, enabling targeted component replacement instead of a full system teardown.
Discussion and Conclusion
The integration of a weighted scoring system with SVM classification provides a robust framework for condition-based maintenance. By prioritizing units in "Abnormal" or "Severe" states, utilities can optimize resource allocation and extend asset life. While the model demonstrates improved diagnostic precision, future work should focus on automating data extraction and conducting more extensive quantitative benchmarking against other machine learning architectures. Ultimately, this research provides a foundation for long-term financial and technical planning for power grid assets.
Summary updated