Swing Node on State Estimation Results with Bad Data and its Error Analysis

Jian Guo, Yin Zhang⋆, Yihang Chen, Ruzhi Xu2015

Abstract

The swing node is the basis of computation for power system state estimation. To analyze its impact, especially when bad data exists near the swing node, this paper presents detailed case studies on whether the swing node should be involved in iterative computations. Three scenarios are examined: bad measurements at the swing node, bad parameters, and bad data at adjacent nodes. Using the IEEE 14-bus system for simulation, error analysis results demonstrate that excluding the swing node from iterations yields superior estimation results.

Introduction

In power system analysis, the swing node (or slack bus) serves as the mathematical anchor, balancing the system's power flow and providing a reference for voltage angles. While its role is well-defined for standard power flow studies, its treatment in State Estimation (SE)—the process of using noisy real-world measurements to determine the most likely state of the grid—is more nuanced. This paper addresses how the choice to include or exclude the swing node in iterative corrections affects the accuracy of the system when "bad data" is present, stemming from faulty sensors or outdated grid models.

Methodology

The researchers utilized the standard Weighted Least Square (WLS) iterative method for state estimation, comparing two distinct approaches:

  1. Involved: The swing node's voltage amplitude is treated as a variable and updated during each iteration (Jacobian matrix dimension $2n-1$).
  2. Not Involved: The swing node's voltage amplitude is held constant as a reference (Jacobian matrix dimension $2(n-1)$).

To test these approaches, controlled errors were introduced: measurement errors (10% to 50% added to voltage and power flow) and parameter errors (modifying line impedance near the swing node).

Experimental Setup

The study used the IEEE 14-bus system, a standard benchmark in power systems research. The system was modified with specific measurement points—6 voltage, 19 active power, and 20 reactive power spots—to ensure observability even under data manipulation.

IEEE 14-bus system configuration with measurement points

Results and Discussion

The "Pollution" Effect

A critical observation is the "pollution" effect: when the swing node is involved in iterations and possesses bad measurement data, the resulting error is not contained. Instead, it spreads to neighboring nodes, leading to a system-wide drop in accuracy. Phase angle errors in other buses tend to increase with their "electrical distance" from the swing node.

Measurement Error Thresholds

The performance gap between the two methods widens as measurement errors increase. As shown in the multi-scenario analysis below, the "not involved" mode consistently maintains lower amplitude and angle errors.

Comparison of amplitude and angle errors across different measurement error levels (10% to 50%)

The results indicate a "breaking point" around 30% error; if the swing node is involved in iterations and its measurement error exceeds this threshold, the state estimator's results become largely meaningless. In contrast, excluding the swing node from iterations consistently produced more stable results across the network.

Parameter vs. Measurement Impact

Interestingly, the study found that small inconsistencies in line parameters (like impedance) have a relatively small impact on the final result regardless of the swing node's status. The primary threat to estimation reliability remains bad measurement data at or near the reference node.

Conclusion

Experimental results show that in cases where bad data is present, not involving the swing node in iterative corrections leads to significantly better estimation results. By holding the swing node voltage constant, the system prevents error propagation from the reference point to the rest of the network. Future research should focus on methods to minimize the "pollution range" of bad data to ensure that single-point failures do not compromise entire grid models.

Summary updated

BibTeX
@misc{guo2015swing,
  author = {Jian Guo and Yin Zhang⋆ and Yihang Chen and Ruzhi Xu},
  title = {{Swing Node on State Estimation Results with Bad Data and its Error Analysis}},
  year = {2015},
  doi = {10.2991/icmii-15.2015.170},
}