Abstract
The quantification of controllability and observability has recently received new interest in the context of large, complex networks of dynamical systems. A fundamental but computationally difficult problem is the placement or selection of actuators and sensors that optimize real-valued controllability and observability metrics of the network. We show that several classes of energy-related metrics associated with the controllability Gramian in linear dynamical systems have a strong structural property, called submodularity, which allows for an approximation guarantee by using a simple greedy heuristic for their maximization. The results are illustrated for randomly generated systems and placement of power electronic actuators in a model of the European power grid.
Introduction
Selecting the best locations for sensors and actuators in large networks, such as electric power grids or biological systems, is a notoriously difficult combinatorial problem. Before designing a control law, engineers must decide where to place these components to maximize "controllability"—the ability to drive the system to a desired state with minimum input energy.
However, choosing a small subset of actuators from a massive pool of possible locations causes a combinatorial explosion. For instance, selecting just 10 locations out of 2,700 possibilities results in approximately $5.6 \times 10^{27}$ combinations. Finding the absolute best combination is NP-hard. While previous research focused on structural controllability (whether a system is controllable at all), this work addresses the harder problem of optimizing energy-related controllability metrics.
Methods: Submodularity and Greedy Optimization
The study bridges control theory and combinatorial optimization by analyzing the controllability Gramian—a matrix defining an ellipsoid in the state space representing reachable states with one unit of input energy.
The core contribution is the mathematical proof that specific scalar functions of this Gramian are submodular. In set theory, submodularity is analogous to the law of diminishing returns: adding an actuator to a small set provides a larger boost to controllability than adding that same actuator to a larger, already-established set.
If a metric is submodular, a standard "greedy" algorithm—which picks the single best actuator at each step—is mathematically guaranteed to achieve at least ~63% ($1 - 1/e$) of the absolute optimal solution. To handle cases where metrics are undefined before full controllability is reached, the authors propose a two-stage greedy algorithm:
- Greedily maximize the rank of the Gramian until the system is fully controllable.
- Greedily maximize the specific energy metric (such as the log determinant) to fine-tune efficiency.
Experimental Validation
The approach was evaluated on two distinct datasets:
Randomly Generated Systems
On a stable linear system with 25 states and 7 actuators, the greedy algorithm was compared against a brute-force calculation of the true optimum. The greedy algorithm didn't just meet the 63% theoretical guarantee; it achieved approximately 98% of the absolute optimal log determinant score, outperforming 99.93% of all possible random actuator combinations.
European Power Grid Model
The algorithm was applied to a simplified linear model of the Continental European power grid consisting of 74 buses. The task was to place 10 High Voltage Direct Current (HVDC) links out of 2,701 possible locations. The greedy approach successfully navigated the massive search space in a computationally feasible timeframe.
Key Insights
- Metric Choice Matters: The authors proved that the negative trace of the inverse Gramian, the log determinant, and the rank are submodular. However, they discovered that the minimum eigenvalue (representing worst-case energy) is not submodular, meaning greedy algorithms may fail for that specific metric.
- Physical Network Impact: Optimizing the log determinant on the power grid resulted in HVDC lines that were long, spread far apart, and evenly distributed. This forces a more balanced, omnidirectional control authority compared to trace-based metrics, which tend to cluster actuators.
Limitations and Future Work
While promising, the study relies on linear system dynamics, which are only approximations of the highly nonlinear dynamics found in real-world power grids. Furthermore, the greedy approach does not strictly guarantee that full controllability will be achieved within a fixed budget of $k$ actuators. Future work will focus on incorporating hard rank constraints and addressing the geographical and financial realities of infrastructure placement.
Summary updated