Study on Nested-Structured Load Shedding Method of Thermal Power Stations Based on Output Fluctuations

Liping Wang, Minghao Liu, Boquan Wang, Jiajie Wu, Chuangang LiEnergies 2017

TL;DR

This paper introduces a novel "Nested-Structured Load Shedding Method" (NSLSM) to improve the accuracy of power and energy balance calculations in power systems. By treating each thermal power station individually and iteratively calculating their peak and non-peak shaving capacities, NSLSM provides a more granular and realistic output process for each station, addressing limitations of traditional methods that group thermal power stations.

What Problem Does This Paper Address?

Ensuring the balance of electric power and energy is crucial for designing and operating power grids efficiently. This involves coordinating the output of various power stations (hydropower and thermal) to meet fluctuating load demands. Existing methods, particularly for thermal power stations (TPS), often group them together, leading to an averaged output that obscures individual station capabilities and can result in suboptimal energy management. A key challenge is accurately modeling the daily and monthly output fluctuations of individual TPS and their contribution to overall system stability, especially considering their inherent limitations in peak shaving compared to hydropower.

Methods

The core contribution is the Nested-Structured Load Shedding Method (NSLSM). This method builds upon the Improved Load Shedding Method (ILSM) but introduces a nested structure for individual TPS. The NSLSM algorithm works as follows:

  1. Monthly Adjustment Coefficient Calculation: A new method is proposed to calculate monthly adjustment coefficients for both hydropower stations and TPS, accounting for monthly fluctuations in load and output.
  2. Iterative Peak and Non-Peak Shaving Capacity Calculation: For each TPS, the NSLSM iteratively calculates its "peak shaving capacity" and "non-peak shaving capacity." This is done by first considering the varying load (peak/waist load) and then the constant base load of the power system.
  3. Individual Output Process Generation: The ILSM is then applied within the NSLSM framework to determine the peak shaving output process and the non-peak shaving output process for each TPS, constrained by their calculated capacities.
  4. Combined Output: Finally, these two processes are combined to generate the typical daily output process for each individual thermal power station.
  5. Calculation Order: The order in which TPS are processed is determined by their available capacity's daily utilized hours, prioritizing those with fewer utilized hours.

This approach contrasts with traditional methods that treat all TPS as a single entity for load shedding.

Datasets

The paper uses data from a region in southwest China for a case study. The datasets include:

  • Maximum monthly load and monthly average load of the power system.
  • Hourly load rate on typical days during flood and non-flood seasons.
  • Monthly average output of hydropower stations.
  • Minimum monthly output of thermal power stations.
  • Installed capacity of each power station.

These datasets are used to validate the proposed NSLSM against the ILSM.

Key Insights and Ideas

  • Granularity Matters: Treating each TPS individually, rather than as a group, provides a more accurate picture of system operation and allows for better utilization of individual station capabilities.
  • Peak Shaving Limitations of TPS: The NSLSM highlights that some TPS have significant limitations in their peak shaving capacity, forcing them to operate at full capacity and leading to increased abandoned hydropower energy.
  • Trade-offs in Energy Management: The NSLSM shows that while it can lead to a higher monthly average output for the overall thermal power group and potentially more abandoned hydropower, it offers a more stable and predictable output process for each individual TPS.
  • Improved Load Shedding for TPS: By nesting the ILSM within a framework that specifically addresses TPS peak shaving constraints, the NSLSM offers a more refined approach to load shedding for these units.

Key Results

The paper presents results comparing the NSLSM with the ILSM for power and energy balance in a dry year.

  • Power Balance: Figures 3 and 4 show that the NSLSM provides a more detailed breakdown of power allocation across individual TPS and hydropower, whereas the ILSM shows a grouped thermal power station output.
  • Energy Balance: Figures 5 and 6 illustrate that the NSLSM can result in a larger amount of abandoned hydropower (Figures 5 shows higher abandoned hydropower from June to August compared to Figure 6). This is attributed to individual TPS being constrained and operating at full capacity.
  • Peak Shaving Capacity: Table 6 demonstrates that the NSLSM can quantify the peak shaving capacity of individual TPS, revealing that only certain TPS (e.g., TPS 1, TPS 2, TPS 5) actively participate in peak shaving during specific months due to their available capacity and calculation order. The ILSM, in contrast, only shows the aggregate peak shaving of the TPSG.
  • Monthly Adjustment Coefficients: Table 7 shows that the monthly adjustment coefficients for all stations are within acceptable limits (<1.2), indicating the feasibility of the proposed method.

Limitations and Future Work

  • Abandoned Hydropower: A noted consequence of the NSLSM is an increase in abandoned hydropower energy, particularly during peak demand periods when individual TPS are constrained. This suggests a potential trade-off between individual station output stability and overall system energy utilization.
  • Coal Consumption and Economic Operation: While the NSLSM provides more accurate output processes, the paper suggests that further research could leverage these results to conduct more detailed studies on coal consumption and the economic operation of individual thermal power stations.
  • Further Optimization: The paper implies that future work could explore optimizing the NSLSM to mitigate the increase in abandoned hydropower while still achieving the benefits of individual station output analysis.

Summary updated

Abstract

The balance of electric power and energy is important for designing power stations’ load distribution, capacity allocation, and future operation plans, and is thus of vital significance for power design and planning departments. In this paper, we analyzed the correlation between the output fluctuations of power stations and the load fluctuations of the power system in order to study the load change of the power system within a year/month/day, and the output variation amongst the power stations in operation. Reducing the output of hydropower stations or increasing the output of thermal power stations (TPS) could keep the monthly adjustment coefficient of the power system within a certain range, and thus balance the power system’s electric power and energy. The method for calculating the balance of electric power and energy of TPS is also improved. The nested-structured load shedding method (NSLSM), which is based on the calculation principle of the load shedding method, is put forward to iteratively calculate the peak shaving capacity and non-peak shaving capacity of every single thermal power station. In this way, the output process of each thermal power station can be obtained. According to the results and analysis of an example, the proposed methods of calculating monthly adjustment coefficients and the balance of electric power and energy of a thermal power station are validated in terms of correctness, feasibility, and effectiveness.
BibTeX
@inproceedings{wang2017study,
  author = {Liping Wang and Minghao Liu and Boquan Wang and Jiajie Wu and Chuangang Li},
  title = {{Study on Nested-Structured Load Shedding Method of Thermal Power Stations Based on Output Fluctuations}},
  booktitle = {Energies},
  year = {2017},
  doi = {10.3390/en10101472},
}
Figure