Study on Energy-Saving Potential Based on Heat and Moisture Transfer Characteristics During Fresh Air Introduction in Deep Underground Engineering

Jiangyan Ma, Xu Zhou, Lin Huang, Baoshun Deng, Lei He, Xiaoling Cao, Shuang QiuEnergies 2025 · DOI

TL;DR

This study investigates how deep underground air tunnels can pre-condition fresh air through heat and moisture transfer with surrounding rock. They found a significant "inlet effect" where air properties stabilize after about 200m, with tunnels providing cooling in summer and heating in winter, offering energy-saving potential for underground buildings.

What Problem Does This Paper Address?

As urbanization pushes development underground, deep-buried buildings are becoming more common. Ensuring good indoor air quality and thermal comfort in these spaces relies heavily on fresh air systems. The pretreatment of this fresh air is crucial for energy efficiency. Underground air tunnels, acting as natural heat exchangers, can leverage the stable thermal properties of the earth to cool air in summer and warm it in winter before it reaches the building. However, the complex interplay of heat and moisture transfer between the airflow and the surrounding rock in these tunnels, especially in deep environments, is not fully understood. This paper aims to fill this gap by clarifying the heat-moisture coupled regulation mechanism and quantifying the energy-saving potential.

Methods

The researchers developed a 2D longitudinal cross-sectional model of a 560m deep, 5m diameter ventilation shaft using COMSOL Multiphysics 6.2. This model incorporated three key physical fields: "Laminar Flow" for airflow, "Heat Transfer in Moist Air" for thermal processes, and "Moisture Transfer in Moist Air" for moisture movement. The model accounts for the coupled heat and moisture transfer between the surrounding rock (treated as an unsaturated porous medium) and the airflow within the tunnel. They established governing equations for both moisture and heat transfer in the surrounding rock, considering liquid water and water vapor phases, and for the airflow itself. The model was validated against field test data from a hydropower air tunnel, showing good agreement. They then simulated the system's performance under various conditions, including different seasons and four typical Chinese cities with varying climate zones.

Datasets

The study utilized actual meteorological data from the ASHRAE 2021 meteorological data test set. For the simulation, they used one year of meteorological data from Chengdu Shuangliu Meteorological Station (Sichuan Province, China) for the primary analysis. For the comparative analysis across different climate zones, they used annual average ground temperatures for Harbin, Nanjing, Beijing, and Guangzhou.

Key Insights and Ideas

  • The "Inlet Effect" is Real and Significant: The first ~200 meters of the tunnel act as a critical zone where the airflow's temperature and humidity adjust significantly due to interaction with the tunnel wall and surrounding rock. Beyond this, conditions stabilize.
  • Seasonal Regulation is Pronounced: In summer, the tunnels effectively cool the incoming fresh air, reducing its temperature by over 1°C and decreasing its enthalpy by up to 3.5 kJ/kg. In winter, they provide a modest heating effect (around -0.6°C temperature rise) and increase enthalpy by about 1 kJ/kg.
  • Surrounding Rock as a Thermal Battery: The surrounding rock exhibits a "summer storage and winter release" characteristic, storing heat during warmer months and releasing it during colder ones, contributing to the tunnel's preconditioning effect.
  • Climate Matters: Higher ground temperatures, like in Guangzhou, significantly reduce the tunnel's preconditioning effectiveness due to weaker heat interaction with the fresh air.
  • Moisture Plays a Key Role: The interaction isn't just about temperature; moisture content in the air and rock also plays a crucial role in the overall heat-moisture regulation, sometimes leading to complex relationships with relative humidity.

Key Results

  • Temperature Stabilization: Tunnel wall temperature stabilizes after approximately 200 meters from the inlet. Humidity stabilization requires a greater depth.
  • Summer Cooling: Airflow temperature decreases by more than 1°C in summer, with an enthalpy reduction of up to 3.5 kJ/kg.
  • Winter Heating: Airflow experiences a slight temperature rise (max ~ -0.6°C) and enthalpy increase (max ~ 1 kJ/kg) in winter.
  • Heat Flux: The inlet effect section shows the highest heat exchange, with boundary heat flux reaching ±4 W/m².
  • Moisture Transfer: In winter, the surrounding rock releases moisture to the airflow (max flux -4.5 × 10⁻⁶ kg/(m²·s)), while in summer, it absorbs moisture (max flux 3 × 10⁻⁶ kg/(m²·s)).
  • Energy Storage: Summer heat storage capacity of the rock is ~2.25 × 10³ kW·h, while winter heat release capacity is ~1.75 × 10³ kW·h.
  • Climate Zone Impact: Guangzhou's high ground temperature leads to a significantly weaker preconditioning effect (max enthalpy difference ~6 kJ/kg in summer, ~4 kJ/kg in winter) compared to other cities.

Limitations and Future Work

The authors acknowledge several limitations:

  • Gravity Ignored: The study did not consider the impact of gravity on liquid water migration.
  • Limited Climate Zones: Only four typical Chinese cities were analyzed, which may not fully represent global climate variations.
  • Lithology Not Considered: The influence of different surrounding rock lithologies on heat-moisture coupled transfer was not investigated.

Future work suggested includes:

  • Incorporating Gravity: Optimizing the model to include gravity effects.
  • Expanding Climate Data: Including more climate zones for broader applicability.
  • Investigating Lithologies: Studying the impact of various rock types.
  • Real-World Validation: Verifying the model with more actual engineering cases to enhance its accuracy for practical design.

Summary updated

Abstract

The goal of this paper is to clarify the heat–moisture coupled regulation mechanism of deep-buried underground air tunnels and to address the research gaps in the heat–moisture coupled transfer between airflow and surrounding rock. This paper established a 560 m deep ventilation shaft with a diameter of 5 m focused on the heat–moisture coupled transfer of “surrounding rock—air tunnel—airflow” to investigate the airflow characteristics; analyze the heat and moisture changes of the tunnel surface and airflow, as well as the energy storage characteristics of the surrounding rock; and compare the induced airflow characteristics across four typical cities in China. The results show the following: there is an “inlet effect” in the deep-buried air tunnel; the wall temperature becomes basically stable after 200 m from the entrance, while a greater depth is required for the stable section of humidity; in summer, the airflow temperature decreases by more than 1 °C and the enthalpy decreases by 3.5 kJ/kg; in addition, the ground temperature in Guangzhou is relatively high, resulting in a limited effect on adjusting the intake airflow. This study aims to provide support for the energy-saving design of fresh air systems in deep-buried underground buildings.
BibTeX
@inproceedings{ma2025study,
  author = {Jiangyan Ma and Xu Zhou and Lin Huang and Baoshun Deng and Lei He and Xiaoling Cao and Shuang Qiu},
  title = {{Study on Energy-Saving Potential Based on Heat and Moisture Transfer Characteristics During Fresh Air Introduction in Deep Underground Engineering}},
  booktitle = {Energies},
  year = {2025},
  doi = {10.3390/en18215684},
}
Figure