STUDY ON CAPTURE PERFORMANCE OF LOCAL EXHAUST HOOD UNDER PASSING AIRFLOW

Miharu Komori, Toshio Yamanaka, Tomohiro Kobayashi, Narae Choi, Noriaki Kobayashi, Yuta SuzukiJournal of Environmental Engineering (Transactions of AIJ) 2023 · DOI

Abstract

In this study, the authors focused on passing airflow, which greatly affects the capture performance of local exhaust hood. In this paper, firstly, capture efficiency and spatial distributions of air velocity and contaminant concentration were measured by experiment to understand the capture performance under passing airflow. Especially, the effect of the passing airflow velocity on the capture efficiency was examined with various hood types. In addition, in order to establish a prediction method for capture performance, a simple prediction model of the airflow under the exhaust hood with passing airflow was studied.

Introduction

Local exhaust hoods are the front line of defense in industrial and laboratory environments, designed to capture pollutants before they disperse into the workspace. However, their performance is notoriously sensitive to "disturbance airflow"—ambient currents caused by HVAC systems, open windows, or personnel movement. While previous research has focused heavily on commercial kitchens where heat creates a natural upward plume (buoyancy) that aids capture, many industrial pollutants are "passive" or isothermal, meaning they do not rise on their own. This study addresses this gap by investigating how different hood geometries handle passive pollutants under varying horizontal crosswind speeds.

Experimental Methodology

The researchers conducted controlled experiments in a circulating wind tunnel at Osaka University. They evaluated five distinct hood geometries: three canopy hoods (90°, 60°, and 10°), a flanged hood, and a simple duct.

Schematic of the experimental wind tunnel setup

To simulate passive contaminants without buoyancy effects, a mixture of Helium and $CO_2$ was calibrated to match the density of air. Capture efficiency ($\eta$) was calculated by comparing $CO_2$ concentrations in the exhaust duct versus the ambient wind tunnel. Spatial velocity and concentration distributions were mapped using ultrasonic anemometers and $CO_2$ sensors. Additionally, the authors proposed a simplified "vector addition" model, combining theoretical suction velocity and horizontal crosswind velocity to predict airflow patterns under the hood.

Results and Discussion

The "Flange Effect"

A critical finding of the study is the superiority of the flanged hood for capturing passive pollutants. The flange acts as a physical barrier that prevents horizontal crosswinds from "sweeping" the pollutant away from the suction zone, effectively extending the hood's reach.

Comparison of Flanged Hood and Simple Duct geometries

The researchers identified a 75% efficiency threshold ($v_{75}$) to compare performance. For a standard 90° canopy, this threshold is reached at a crosswind of only 0.29 m/s. In contrast, the flanged hood maintains efficiency above 75% even at crosswinds of 0.5 m/s. Interestingly, the 60° canopy performed worse than the 90° version, likely due to airflow detachment at the edges creating turbulence that pulls pollutants out of the hood.

Critical Performance Factors

  • Source Proximity: The distance between the pollutant source and the duct opening ($\Delta H$) is the most critical factor. When the source is very close ($\Delta H = 100mm$), almost any hood geometry is effective. As distance increases, the performance of non-flanged hoods drops significantly.
  • Buoyancy vs. Momentum: While heat-driven plumes assist capture at low wind speeds, this advantage disappears as crosswinds increase. At higher speeds, the horizontal momentum of the air overrides the vertical lift of the heat.
  • Model Accuracy: The simplified vector addition model accurately predicted airflow near the duct opening but struggled to account for the "wake" or recovery of wind speed on the downstream side of the hood structure.

Conclusion

This research demonstrates that flanged hoods are significantly more robust than standard canopy designs in environments with significant crosswinds. While the simplified airflow model provides a good baseline for prediction, future work will focus on refining it to account for complex turbulence and downstream wake effects. The ultimate goal is to develop design tools that can predict pollutant dispersion without the need for intensive Computational Fluid Dynamics (CFD) simulations.

Summary updated

Abstract

In this study, the authors focused on passing airflow, which greatly affects the capture performance of local exhaust hood. In this paper, firstly, capture efficiency and spatial distributions of air velocity and contaminant concentration were measured by experiment to understand the capture performance under passing airflow. Especially, the effect of the passing airflow velocity on the capture efficiency was examined with various hood types. In addition, in order to establish a prediction method for capture performance, a simple prediction model of the airflow under the exhaust hood with passing airflow was studied.
BibTeX
@article{komori2023study,
  author = {Miharu Komori and Toshio Yamanaka and Tomohiro Kobayashi and Narae Choi and Noriaki KOBAYASHI and Yuta Suzuki},
  title = {{STUDY ON CAPTURE PERFORMANCE OF LOCAL EXHAUST HOOD UNDER PASSING AIRFLOW}},
  journal = {Journal of Environmental Engineering (Transactions of AIJ)},
  year = {2023},
  doi = {10.3130/aije.88.587},
}

Loading related content...

Figure