Study of the Protection and Energy Transmission Modes of One Phase Short Circuit to Ground in Inverters

Dezhi Chen, Zhixiang Zhang, Shichong Zhang, Yun Sun, Wenbo Zhao, Wenliang Zhao2023 · DOI

TL;DR

This paper investigates the critical issue of single-phase-to-ground short circuits in inverters, which can lead to damaging overvoltage and overcurrent. The authors propose a method for designing DC bus capacitors and reactors to mitigate these faults, demonstrating its effectiveness through simulations and experiments on a 110 kW inverter.

What Problem Does This Paper Address?

Inverters, particularly those employing complex PWM control strategies, are prone to failure. A significant threat is the single-phase-to-ground short circuit, which can subject crucial components like rectifier diodes and IGBTs to excessive voltage and current. Existing research on DC bus capacitor and reactor design often overlooks this specific fault scenario, leaving a gap in ensuring inverter reliability under such conditions. This paper aims to fill that gap by providing a systematic approach to designing these components with single-phase-to-ground faults in mind.

Methods

The paper employs a multi-faceted approach:

  • Analytical Design of DC Bus Capacitance: The authors utilize the Newton-Raphson method to calculate DC bus capacitance, considering factors like voltage, volume, temperature, power consumption, and lifetime. This involves analyzing the capacitor's charging and discharging processes and ripple current.
  • DC Reactor Design: The design of the DC reactor focuses on two key aspects: ensuring system stability and limiting voltage drop, and extending the life of the bus capacitor by managing ripple current. This involves using small-signal analysis to derive the characteristic equation of the circuit transfer function and considering empirical rules for inductance values.
  • Electromagnetic Design of DC Reactor: The paper details the electromagnetic design of the DC reactor, including selecting core material (35Z155 silicon steel sheet), core type (EI type), and calculating parameters like turns, air gap, and window occupancy rate.
  • Simulation and Experimental Verification: The proposed design methodology is validated through simulations using MATLAB/Simulink and experimental tests on a 380 V/110 kW inverter. The experiments specifically focus on the single-phase-to-ground short circuit scenario.

Datasets

Not discussed in the paper.

Key Insights and Ideas

  • The critical role of DC bus components in fault mitigation: The study highlights that proper design of DC bus capacitance and inductance is not just for normal operation but is crucial for surviving severe fault conditions like single-phase-to-ground shorts.
  • Newton-Raphson for capacitance design: Applying the Newton-Raphson method provides a systematic way to determine DC bus capacitance, considering multiple operational and longevity parameters.
  • Balancing reactor inductance: The paper emphasizes the trade-offs in DC reactor inductance – too small leads to excessive ripple and capacitor loss, while too large can cause voltage drops and instability.
  • Impact of leakage inductance: The study acknowledges the influence of power transformer leakage inductance on the double boost circuit during short circuits.
  • Symmetrical DC reactor placement: The experimental results suggest that halving the DC reactor value and placing it symmetrically on both the positive and negative DC buses leads to more balanced current distribution and improved performance during faults.

Key Results

  • The paper proposes an analytical method for calculating DC bus capacitance and reactor parameters.
  • A 380 V/110 kW inverter was developed and tested.
  • Experimental results demonstrate that when a DC reactor is installed on both sides of the DC bus, the current and voltage through rectifiers, DC bus, and diodes decrease significantly during a single-phase-to-ground short circuit.
  • Specifically, in one experiment, placing a DC reactor on both the anode and cathode of the DC bus reduced the output current of the short circuit phase to 141 A (from 433.3 A without this configuration) and the DC bus voltage to 652 V (from 829.16 V). The diode reverse voltage also decreased to 1117 V (from 1604 V).

Limitations and Future Work

  • Parasitic Parameters: The paper notes that real-world experimental results can be "worse practically due to the parasitic parameters," suggesting that a more comprehensive model might be needed for absolute precision.
  • Future Design Considerations: The authors suggest that in future designs, the impact of short-circuit to ground should be explicitly considered, and rectifier modules with higher withstand voltages (e.g., >1600 V) should be selected. They also recommend designing the DC reactor as a double wound group for each positive and negative bus.
  • Further Analysis: The paper mentions that further analysis without a reactor, considering the influence of a power transformer, when a phase-to-ground short circuit occurs, is possible.

Summary updated

BibTeX
@misc{chen2023study,
  author = {Dezhi Chen and Zhixiang Zhang and Shichong Zhang and Yun Sun and Wenbo Zhao and Wenliang Zhao},
  title = {{Study of the Protection and Energy Transmission Modes of One Phase Short Circuit to Ground in Inverters}},
  year = {2023},
  doi = {10.3390/s23198211},
}

Loading related content...

Figure