Single Line-to-Ground Fault Type Multilevel Classification in Distribution Network Using Realistic Recorded Waveform

Jiajun Liu, Chenjing Li, Yue Liu, Ji Sun, Haokun Lin2023

TL;DR

This paper introduces a novel, multi-level classification method for six types of single line-to-ground faults (SLGFs) in distribution networks, utilizing realistic recorded waveforms. By analyzing zero-sequence voltage and current characteristics, the method achieves high accuracy and robustness, addressing a critical need for precise fault identification in power systems.

What Problem Does This Paper Address?

Single line-to-ground faults (SLGFs) are the most common type of fault in distribution networks, accounting for up to 80% of all incidents. Accurately identifying the type of SLGF is crucial for effective fault diagnosis, targeted remediation, and preventing cascading failures. However, existing methods often struggle with distinguishing between various SLGF subtypes, especially those involving transition resistance, arcing, intermittency, or transient phenomena. Furthermore, obtaining realistic datasets that encompass these diverse fault types has been a significant challenge, limiting the development and validation of robust classification algorithms. This paper aims to bridge this gap by proposing a comprehensive, multi-level classification approach that leverages real-world fault data.

Methods

The core of this paper is a four-criterion, multi-level classification strategy designed to distinguish between six types of SLGFs: Small-Impedance Fault (SIF), Medium-Impedance Fault (MIF), High-Impedance Fault (HIF), Arc Grounding Fault (AGF), Intermittent Grounding Fault (IGF), and Transient Grounding Fault (TGF).

  1. Criterion 1 (Peak Distribution Matrix): This criterion utilizes Variational Mode Decomposition (VMD) to analyze the zero-sequence current (ZSC) waveform. The ZSC is decomposed into three modes, with the high-frequency component (IMF2) being particularly informative. By counting the number of peaks in the envelope of IMF2 within specific periods, AGFs and IGFs (which exhibit multiple transient processes) are initially grouped together (Label I), distinct from other fault types (Label II).
  2. Criterion 2 (Permutation Entropy): To differentiate between AGFs and IGFs within Label I, permutation entropy is applied to the ZSC. This metric quantifies the complexity of the time series. AGFs, with their more complex arcing and reignition states, exhibit higher permutation entropy values than IGFs.
  3. Criterion 3 (ZSV Attenuation Degree): For faults in Label II, this criterion focuses on the zero-sequence voltage (ZSV) during the fault recovery period. The attenuation degree of the ZSV is calculated. If the ZSV decays significantly (to less than 5% of its initial value) over a defined number of periods, the fault is classified as a Transient Grounding Fault (TGF). Otherwise, it's considered a Transition Resistance Grounding Fault (TRGF).
  4. Criterion 4 (Transition Conductance): This criterion further classifies TRGFs (SIFs, MIFs, and HIFs) based on their transition resistance. It leverages the relationship between the fault transition conductance, the variation in ZSV, and the fault phase voltage. A parameter, Kset, is derived, which is inversely proportional to transition resistance. Thresholds for Kset are established to distinguish between SIFs, MIFs, and HIFs.

The method is designed as a decision-tree-like process, progressively narrowing down the fault type based on these criteria.

Datasets

The paper utilizes realistic recorded waveforms from actual single line-to-ground faults (SLGFs) in the Xinjiang distribution network in China. These datasets encompass the six fault types (SIF, MIF, HIF, AGF, IGF, and TGF) that the proposed method aims to classify. The authors also conducted simulations on a radial distribution network model and an IEEE-13 node unbalanced load network model to verify the method's universality.

Key Insights and Ideas

  • Multi-level classification is essential: No single feature is sufficient to distinguish all six SLGF types. A hierarchical approach, progressively analyzing different aspects of the ZSC and ZSV, is necessary.
  • VMD for transient analysis: Variational Mode Decomposition proves effective in isolating informative frequency components of the ZSC, particularly the high-frequency transient signals crucial for initial fault grouping.
  • Permutation entropy as a complexity measure: Permutation entropy is a powerful tool for quantifying the intricate dynamics of AGFs, allowing their differentiation from less complex IGFs.
  • ZSV decay as a TGF indicator: The characteristic attenuation pattern of the ZSV during fault recovery provides a reliable method for identifying transient grounding faults.
  • Transition conductance linkage: The derived relationship between transition conductance, ZSV variation, and fault phase voltage offers a direct way to classify faults based on their resistance levels (SIF, MIF, HIF).
  • Robustness to real-world conditions: The method demonstrates good performance even when subjected to simulated noise and data loss, highlighting its practical applicability.

Key Results

The proposed multi-level classification method achieved correct classification for all six SLGF types across various test scenarios:

  • Radial Distribution Network: The method correctly classified all simulated faults.
  • Unbalanced Load Network: The method also correctly classified all simulated faults in the IEEE-13 node model.
  • Practical Fault Data Verification: When applied to actual recorded data from the Xinjiang distribution network, the method successfully identified all six fault types, demonstrating its engineering applicability.
  • Robustness: The method maintained high classification accuracy even with the introduction of Gaussian white noise (20 dB SNR) and simulated data loss (5% data loss).

Limitations and Future Work

The authors acknowledge that some criteria require sufficient data to set accurate thresholds for different network configurations. Their future work will focus on:

  • Deepening fault characteristic analysis: Further investigation into the inherent characteristics of faults.
  • Reducing data dependency: Aiming to minimize the reliance on large datasets for threshold setting, making the method more adaptable to diverse power systems.

Summary updated

BibTeX
@misc{liu2023single,
  author = {Jiajun Liu and Chenjing Li and Yue Liu and Ji Sun and Haokun Lin},
  title = {{Single Line-to-Ground Fault Type Multilevel Classification in Distribution Network Using Realistic Recorded Waveform}},
  year = {2023},
  doi = {10.3390/s23218948},
}