Sampling Time Error Correction Method in Synchronized Phasor Measurement Using Akima Piecewise Cubic Hermite Interpolation
Abstract
Abstract This paper introduces a novel method for synchronized phasor measurement, employing soft synchronized sampling with temporal pulse signals like Pulse Per Second (PPS) from GPS as the time reference. The method begins by detecting and characterizing sampling time errors in the local oscillator relative to the GPS pulse signals. These errors are then corrected using Akima piecewise cubic Hermite interpolation, effectively aligning the sampling instances to an ideal timing grid. The corrected data are processed using a Recursive DFT algorithm to extract synchronized phasors with high precision. Compliance with the C37.118.1 standard is demonstrated by evaluating critical metrics such as frequency, phase angle, and Total Vector Error (TVE). The results highlight the accuracy and efficiency of this software-centric approach, offering a cost-effective and scalable solution compared to conventional hardware-intensive methods for power grid phasor measurement.
BibTeX
@article{yin2025sampling,
author = {Xiaodong Yin and Changxi Yue and Siyuan Liang and Yao Li and Wei Liu and Jicheng Yu},
title = {{Sampling Time Error Correction Method in Synchronized Phasor Measurement Using Akima Piecewise Cubic Hermite Interpolation}},
journal = {Journal of Physics Conference Series},
year = {2025},
doi = {10.1088/1742-6596/3012/1/012014},
}Ask Althea to put this paper to the test.