Safety Analysis of Double Grounding Mode for Maintenance of Active Distribution Networks

Jun Chen, Xuanqing Zhou, Jian Sun, Qinghua Chen2025

Abstract

At present, high distributed generators (DG) permeability will increase the safety risk of “mis-power transmission” or “ reverse power transmission” in the maintenance operation of active distribution networks. This paper adopts a double grounding mode, and then uses the superposition theorem analyze the residual voltage of the grounding wire under different working conditions of the 10 KV line when there is three-phase mis-power transmission upstream/downstream, uses the complex sequence network to analyze the relationship among distributed (DG) power source size, other factors and residual voltage of the grounding wire under different working conditions of the 10 KV line when there is single-phase mis-power upstream/downstream. Finally, the residual voltage of the grounding wire is compared with the safe voltage of the human, and the safety criterion of the double grounding wire of the source-containing distribution network is improved, and it is concluded that the single-phase mis-power transmission working condition can be prevented in by double grounding mode.