TL;DR
This paper investigates the critical issue of arc reignition in 750 kV AC filter circuit breakers during opening operations, which can lead to equipment failure. By using PSCAD/EMTDC simulations, the researchers analyzed the impact of mechanical dispersion, opening phase angle, and operating speed on reignition and proposed mitigation strategies, finding that a combined "phase-selective opening with controlled opening speed" is most effective for most filter types.
What Problem Does This Paper Address?
High-voltage direct current (HVDC) transmission systems rely heavily on converter stations, which consume significant reactive power and generate harmonics. To manage this, AC filter banks are essential, but their frequent switching by circuit breakers can cause severe transient overvoltages and inrush currents. Recent years have seen an increase in circuit breaker failures during the opening process, specifically linked to arc reignition phenomena. This paper aims to understand the underlying causes of this reignition in 750 kV AC filter circuit breakers and to evaluate methods for suppressing these damaging transients.
Methods
The study employs PSCAD/EMTDC V5.0 for electromagnetic transient simulations. A key aspect of their methodology is the development of a detailed simulation model for the circuit breaker's opening process, incorporating:
- Arc Reignition Module: This module integrates gas dielectric theory and energy recovery theory to model arc burning and extinction. It uses a critical breakdown field strength calculation based on SF6 gas properties and a dynamic breakdown voltage model derived from three-dimensional electric field simulations and fitting of experimental data.
- Mayr Arc Model: This classic model is used to simulate the dynamic arc behavior, including ignition, steady-state burning, and extinction.
- Parameter Variation: The researchers systematically varied key parameters to understand their impact:
- Mechanical Dispersion: Simulations were performed with mechanical dispersions of ±0.5 ms, ±1 ms, and ±2 ms to assess the effect of imperfect synchronization between circuit breaker fractures.
- Opening Phase Angle: The influence of different switching angles (0° to 360°) on reignition was investigated.
- Operating Speed: The impact of varying opening speeds (5 m/s to 10 m/s) was analyzed.
- Mitigation Strategies: Two strategies were compared:
- "Phase-selective opening"
- "Phase-selective opening combined with controlled opening speed"
Datasets
Not discussed in the paper. The study relies on simulation models built upon the Lingzhou-Shaoxing ±800 kV HVDC transmission project's actual circuit configuration.
Key Insights and Ideas
- Mechanical Dispersion is Critical: Even small mechanical dispersions in the circuit breaker's operating mechanism can lead to one fracture bearing the entire source voltage, significantly increasing the number of arc reignition events. The longer this condition persists, the more reignitions occur.
- Opening Phase Angle Matters: The timing of the breaker opening relative to the AC voltage waveform (opening phase angle) has a substantial impact on the contact voltage difference at the moment of opening, directly influencing the likelihood and severity of arc reignition.
- Opening Speed Influences Dielectric Recovery: The speed at which the breaker contacts separate affects the SF6 gas dielectric recovery rate, which in turn influences the number of arc reignition events.
- Filter Type Dictates Strategy: The effectiveness of mitigation strategies varies significantly between different filter types (BP11/13, HP24/36, HP3, and SC). While a combined approach works well for most, the SC filter shows less benefit from the "controlled opening speed" component.
Key Results
- Mechanical Dispersion: Increasing mechanical dispersion (up to ±2 ms) led to a slight increase in inrush current and overvoltage, but the primary impact was on the number of arc reignition events, particularly in the early opening stage.
- Opening Phase Angle: Simulations across 360° showed that different phase angles resulted in varying inrush currents and overvoltages. For instance, the SC filter exhibited a wide range of inrush currents (up to 23.82 kA) and consistently low overvoltages (max 635.61 kV), while HP3 and BP11/13 filters showed higher overvoltages (up to 1248.40 kV and 1347.47 kV, respectively).
- Operating Speed: Higher opening speeds generally led to lower inrush currents and overvoltages for most filter types, though specific optimal speeds were identified for each. For example, the HP3 filter showed relatively small transients at high speeds, while the SC filter's inrush current varied significantly with speed.
- Mitigation Strategies:
- For BP11/13, HP24/36, and HP3 filters, the "phase-selective opening combined with controlled opening speed" strategy provided superior suppression of inrush currents and overvoltages compared to "phase-selective opening" alone.
- For SC filters, the combined strategy offered no significant improvement in overvoltage, and while it slightly reduced inrush current, "phase-selective opening" alone was deemed more practical and economical.
Limitations and Future Work
- Limitations: The study acknowledges that the "opening speed + phase-selective opening" strategy, while effective for some filters, incurs additional costs and complexity due to extra control devices. For SC filters, the benefit of adding controlled opening speed is not significant enough to justify the added cost.
- Future Work: The authors suggest future research could involve:
- Integrating advanced control algorithms or real-time monitoring systems for dynamic adjustment of breaker operating parameters.
- Conducting experimental validation of the proposed strategies under a wider range of operating conditions to enhance practical applicability.
Summary updated