Research on Improved Auto-Tuning of a PID Controller Based on Phase Angle Margin

Deliang Zeng, Zheng Yan-qiu, Wei Luo, Yong Hu, Qingru Cui, Qing Li, Chen PengEnergies 2019 · DOI

TL;DR

This paper presents an improved auto-tuning method for PID controllers, specifically addressing the challenges of tuning controllers for thermal power plants which often exhibit first-order plus dead-time (FOPDT) characteristics. By optimizing the target phase angle margin selection and incorporating a plant identification step, the proposed method achieves better control performance with faster response and reduced overshoot compared to traditional methods.

What Problem Does This Paper Address?

Tuning PID controllers for industrial processes, especially in thermal power plants, is crucial for maintaining stable and efficient operation. However, traditional tuning methods like Ziegler-Nichols (Z-N) can be disruptive and may not perform optimally for plants with significant delays. The phase angle margin (PM) method offers better stability but struggles with plants that have large time delays, leading to oscillations or even divergence in the system's response. This paper aims to overcome these limitations by proposing an enhanced PM auto-tuning method that is more robust and effective for FOPDT systems commonly found in thermal power plants.

Methods

The core of this research is an improved Phase Angle Margin (PM) auto-tuning method. The authors first analyze the shortcomings of the traditional PM method, particularly its inability to guarantee good control for plants with large delays and its reliance on accurate plant models. The proposed method introduces several key enhancements:

  • Optimized Target Phase Angle Margin Selection: Instead of a fixed value, the target phase angle margin is determined based on the frequency characteristics of the controlled plant, ensuring critical oscillation is achievable and stable.
  • Plant Identification: The method incorporates a step to identify the plant's mathematical model (specifically, its gain, time constant, and delay time) using the oscillation curve generated by the relay feedback loop. This is achieved through analyzing the amplitude and angular frequency of the oscillation.
  • Correction Coefficient Optimization: A genetic algorithm is employed to optimize a correction coefficient (β) in the PM tuning formula. This optimization aims to minimize the Integrated Time Absolute Error (ITAE) index, a common metric for evaluating control system performance.

The overall process involves using a relay to induce limit oscillations, identifying the plant model from these oscillations, calculating initial PID parameters using the improved PM formula with an optimized correction coefficient, and finally, evaluating the performance using the ITAE index.

Datasets

Not discussed in the paper. The paper uses simulated models of thermal power plant systems (e.g., main steam temperature control, secondary spray cooling system) and a generalized plant model for evaluation.

Key Insights and Ideas

  • The "one-size-fits-all" approach to PID tuning is insufficient: The paper highlights that a single correction factor (β) in the traditional PM method cannot guarantee satisfactory control for diverse plant characteristics, especially those with significant delays.
  • Plant identification is crucial for robust auto-tuning: By identifying the plant's parameters (gain, time constant, delay), the auto-tuning algorithm can adapt more effectively, leading to better performance.
  • Optimizing the phase angle margin is key: Dynamically selecting the target phase angle margin based on plant characteristics, rather than using a fixed value, improves the likelihood of achieving stable critical oscillations and better overall control.
  • ITAE as an optimization target is effective: Using ITAE as the objective function for optimizing the correction coefficient leads to PID controllers that exhibit faster response and lower overshoot.

Key Results

The improved PM auto-tuning method demonstrated superior performance compared to the traditional PM method and the Ziegler-Nichols (Z-N) method in both simulations and a real-world experiment on a 1000 MW ultra-supercritical unit.

  • Simulation Results: The improved PM method achieved a significantly smaller ITAE index (942.13) compared to the traditional PM method (12841) and Z-N method (6944.2). The control curves showed minimal overshoot (around 1%) and a faster adjustment time (approximately 100 s).
  • Experimental Results: An experiment on a 1000 MW ultra-supercritical unit's main steam temperature control system showed that the improved algorithm could safely and effectively tune the PID controller. The oscillation amplitude during tuning was within acceptable limits (<2 °C), and the system responded well to setpoint changes, stabilizing quickly.

Limitations and Future Work

  • Limitations:
    • The paper focuses on First-Order Plus Dead Time (FOPDT) models, which are common but not universally applicable to all thermal power plant systems.
  • While the method is shown to be effective, the complexity of the plant identification step might be a consideration for very rapid online tuning requirements.
  • The paper mentions that the correction coefficient (β) traverses a range of (0,10), but the specific optimization process and its computational cost are not elaborated in detail.
  • Future Work:
    • Extending the method to handle more complex plant models beyond FOPDT.
  • Investigating further optimization of the auto-tuning speed and computational efficiency.
  • Exploring the application of this improved method to other types of industrial control systems.

Summary updated

Abstract

In order to realize fast and efficient tuning of the proportional-integral-derivative (PID) controller parameters in thermal power plants, this paper thoroughly analyzes the problems existing in the relay characteristic method based on the phase angle margin auto-tuning method (PM method), and proposes an improved PM auto-tuning method for the most common first order plus dead time (FOPDT) model in practical engineering applications. The improved algorithm proposes the design of the target phase angle margin and the method of plant identification. Then, the optimization algorithm is used to calculate the correction coefficient of the setting formula to obtain the PID controller parameters that minimize the integrated time absolute error (ITAE) index of the control system. Finally, through the auto-tuning experiment on the generalized control model of the main steam temperature system in thermal power plants, it is verified that the improved algorithm is superior to the traditional PM method and Ziegler–Nichols method (Z-N method), and can obtain a fast and stable control performance.
BibTeX
@inproceedings{zeng2019research,
  author = {Deliang Zeng and Zheng Yan-qiu and Wei Luo and Yong Hu and Qingru Cui and Qing Li and Chen Peng},
  title = {{Research on Improved Auto-Tuning of a PID Controller Based on Phase Angle Margin}},
  booktitle = {Energies},
  year = {2019},
  doi = {10.3390/en12091704},
}
Figure