Reliability centered condition-based maintenance of zinc oxide lightning arresters: concept, process and case study

Fan Yang, Rui Han, Yu Zheng, Peng Jiang, Wenhao Wang, Xuzhu DongFrontiers in Energy Research 2024 · DOI

Abstract

Ensuring the reliability of power grid equipment is fundamental to grid stability. Zinc oxide (ZnO) lightning arresters are critical for limiting overvoltage, yet traditional maintenance relies on infrequent, invasive offline tests. This study proposes a Reliability Centered Condition-Based Maintenance (RCCM) framework. By analyzing a decade of fault data, identifying effective state quantities, and developing a health evaluation model, the research demonstrates a transition toward more efficient, data-driven maintenance. Results show that the proposed RCCM method reduces workload and improves maintenance efficiency in actual power grid operations.

Introduction

As power grids expand, the volume of equipment requiring maintenance often exceeds available resources. Zinc oxide lightning arresters serve as the primary defense against overvoltage events, such as lightning strikes or switching surges. Traditionally, these devices are evaluated through "preventive tests" that necessitate power outages. These outages, while intended to ensure safety, ironically reduce the very grid reliability the arresters are meant to protect.

The internal structure of a zinc oxide lightning arrester.

The challenge lies in bridging the resource gap—maintaining more equipment with fixed budgets—and the accuracy gap—assessing health using online data rather than infrequent offline measurements.

Methods and Data

The proposed RCCM framework follows a five-stage process: fault mode analysis, state quantity screening, status evaluation, maintenance decision-making, and reliability feedback. The technical core is a health evaluation model that uses "segmented deduction functions" for critical metrics. Unlike simple binary thresholds, this model reflects the non-linear risk of equipment failure.

The non-linear U-I characteristic curve of a zinc oxide resistor.

The study utilized a 10-year dataset of lightning arrester faults (110 kV and above) from a Chinese province. This data allowed researchers to correlate online metrics with traditional offline tests. The zinc oxide valve plate, shown in Figure 2, exhibits a highly non-linear voltage-current (U-I) relationship, which is fundamental to its protective function.

Key Insights and Results

Analysis of the decade-long dataset revealed several critical findings:

  • The 15-Year Rule: Approximately 80% of faults occurred in arresters with less than 15 years of service, suggesting that manufacturing, installation, and environmental factors are more significant than simple aging.
  • Sealing as a Root Cause: Sealing failures often lead to moisture ingress, which subsequently causes valve degradation and thermal runaway. Catching these issues early via temperature rise can prevent catastrophic failure.
  • Online Monitoring Effectiveness: Temperature rise and resistive current were found to be highly effective proxies for internal health, identifying the majority of faults without requiring a power outage.

In a validation case, a 500kV arrester was flagged as "Serious" by the RCCM model due to abnormal resistive current and local overheating. Subsequent disassembly revealed a displaced sealing ring, confirming the model's diagnosis before a total failure occurred.

Conclusion

The RCCM framework provides a robust pathway for transitioning from scheduled to condition-based maintenance. By leveraging online monitoring and non-linear scoring models, utilities can improve grid reliability while optimizing maintenance resources. Future work will focus on expanding the dataset to further refine the health evaluation functions and validating the model across diverse grid environments.

Summary updated

Abstract

Introduction: The reliability of power equipment is the foundation for maintaining the reliability of the power grid. As a core device for limiting overvoltage in the power grid, lightning arresters have received widespread attention, and ensuring their reliability is crucial. Methods: To improve the reliability of zinc oxide surge arresters in the power system, the fault characteristics and health assessment methods of zinc oxide surge arresters were studied using reliability centered condition-based maintenance(RCCM). Firstly, the fault characteristic of zinc oxide lightning arresters in operation over years were collected and analyzed from different aspects. Then the effective state quantities corresponding to different types of defects and their detection methods were proposed. The health status evaluation model for zinc oxide lightning arrester was established, and the effectiveness of the evaluation model was verified through fault cases. Results and Discussion: It shows that the proposed state quantities and RCCM method are suitable for the actual operation and maintenance of zinc oxide lightning arresters. It can reduce the workload and improve the efficiency of existing operation and maintenance of lightning arresters.
BibTeX
@inproceedings{yang2024reliability,
  author = {Fan Yang and Rui Han and Yu Zheng and Peng Jiang and Wenhao Wang and Xuzhu Dong},
  title = {{Reliability centered condition-based maintenance of zinc oxide lightning arresters: concept, process and case study}},
  booktitle = {Frontiers in Energy Research},
  year = {2024},
  doi = {10.3389/fenrg.2024.1359849},
}