TL;DR
This paper introduces a novel primal-dual (P-D) formulation to accurately price Short-Circuit Current (SCC) services from synchronous generators (SGs) while preserving the crucial integrality constraints of Unit Commitment (UC). This approach ensures revenue adequacy for generators and provides interpretable SCC prices, overcoming limitations of existing methods that either relax integrality or bundle prices, leading to market inefficiencies.
What Problem Does This Paper Address?
The increasing penetration of Inverter-Based Resources (IBRs) in power grids is leading to a decline in the Short-Circuit Current (SCC) provided by traditional Synchronous Generators (SGs). SCC is vital for the reliable operation of protection devices. As SGs are phased out, ensuring sufficient SCC becomes a challenge. Pricing this critical ancillary service is complicated by the inherent non-convexity introduced by the binary commitment decisions in Unit Commitment (UC) problems. Existing methods like "dispatchable pricing" relax these binary constraints, losing crucial information about the system's actual operating state and potentially leading to inaccurate prices or requiring uplift payments. "Restricted pricing" bundles SCC prices with other services, reducing interpretability and failing to remunerate units without commitment variables, such as synchronous condensers. This paper aims to bridge this gap by developing a pricing mechanism that accurately reflects SCC's value while respecting the discrete nature of UC.
Methods
The core of this paper is the development of a Primal-Dual (P-D) formulation for SCC-constrained Unit Commitment. Here's a breakdown of the approach:
- Preserving Integrality: Unlike dispatchable pricing, the P-D formulation retains the binary nature of UC variables in the primal problem.
- Dual Formulation: The authors derive the dual of a relaxed SCC-constrained UC problem. This relaxation allows for the computation of shadow prices (dual variables) for the SCC constraints.
- Non-Negative Profit Constraint: A key innovation is the inclusion of a non-negative profit constraint for thermal units. This ensures that generators can recover their operating costs (energy and startup) through a combination of energy and SCC revenues. This constraint links the primal and dual problems.
- Minimizing the P-D Gap: The objective of the P-D formulation is to minimize the "P-D gap," which is the difference between the primal and dual objective functions. This minimization, coupled with the non-negative profit constraint, allows for the joint optimization of operating points and market clearing prices.
- Linearization Techniques: To handle non-linear terms arising from the SCC constraints (specifically, products of binary variables and continuous variables), the authors employ linearization techniques like McCormick envelopes and binary expansion.
Datasets
The case studies are conducted on a modified IEEE 30-bus system. This system is augmented with Inverter-Based Resources (IBR) at specific buses ({1, 23, 26}) and Synchronous Generators (SGs) at other buses ({2, 3, 4, 5, 27, 30}), with each bus hosting two SGs. The parameters for SGs are provided in Table II. The SCC coefficients (K) were computed based on prior work [18]. The code used for the simulations is publicly available in repository [15].
Key Insights and Ideas
- Integrality Matters for Pricing: Relaxing UC integrality, as done in dispatchable pricing, leads to inaccurate SCC prices that can underestimate the service's true value and fail to ensure generator profitability.
- Explicit SCC Pricing is Crucial: The P-D method provides explicit, interpretable prices for SCC, which is essential for remunerating units that provide this service, especially those without commitment variables (like synchronous condensers).
- Non-Negative Profit Drives Market Equilibrium: The inclusion of a non-negative profit constraint is vital for achieving a market equilibrium where all generators are incentivized to participate and recover their costs.
- SCC as a Byproduct vs. a Service: The P-D method captures the dual role of SGs: providing energy as a primary function and SCC as a byproduct or a dedicated service. This nuanced understanding leads to more efficient pricing.
- Bus-Specific SCC Needs: The analysis highlights that only specific "risky" buses require dedicated SCC procurement, while others can benefit from the SCC provided by these critical units.
Key Results
- Revenue Adequacy: The proposed P-D pricing method ensures that generators can achieve non-negative profits, eliminating the need for uplift payments.
- Accurate SCC Prices: The P-D method generates more accurate and interpretable SCC prices compared to dispatchable and restricted pricing methods. For instance, in the multi-period analysis, the dispatchable method underestimated SCC prices for critical units, leading to negative total profits.
- Improved System Security: By ensuring adequate SCC through proper pricing, the P-D method helps maintain system security and the reliability of protection devices.
- Reduced Price Spikes: The P-D method avoids spurious SCC price signals at buses that do not critically need the service, unlike the dispatchable method.
- Computational Tractability: Despite preserving integrality, the P-D formulation, after linearization, results in an MILP that is computationally tractable.
Limitations and Future Work
- Limitations:
- The paper focuses on three-phase nodal short-circuit faults.
- The SCC coefficients (K) are approximated using a data-driven approach, which might introduce some error.
- The "restricted pricing" method is shown to be unsuitable for remunerating SCC, especially for synchronous compensators.
- Future Work:
- Extend the primal-dual formulation to include other ancillary services involving binary variables, such as voltage stability.
- Develop a holistic pricing framework that integrates multiple ancillary services.
- Investigate the extension of the primal-dual formulation to other types of faults.
Summary updated