NeurIPS 2026Coming to NeurIPS?Explore papers, orals & directions

Predictive Maintenance of VRLA Batteries in UPS towards Reliable Data Centers

Jingxian Tang, Jin‐Hong Du, Yiting Lin, Qing‐Shan JiaIFAC-PapersOnLine 2020

Abstract

The reliability of data centers can be severely affected when battery failure occurs in the Uninterruptible Power Supply (UPS). Thus it has become a central issue for the industry to discover failure-impending batteries in UPS. In this paper, we consider this important problem and present a data-driven method for predictive battery maintenance. The major contributions are as follows.First, we develop a changepoint detection technique for efficient data labeling. Second, new features are designed to fully utilize the dataset. Third, we build a predictive classification model which can discriminate between healthy and failure-impending batteries. Our method has been built and evaluated on 209,912,615 records from Tencent data center involving nearly 300 batteries monitored over 2 years. The experiment on test set shows that our method is able to predict battery replacement with 98% accuracy and averagely 15 days in advance, which outperforms the previous maintenance policy by more than 8%.
BibTeX
@inproceedings{tang2020predictive,
  author = {Jingxian Tang and Jin‐Hong Du and Yiting Lin and Qing‐Shan Jia},
  title = {{Predictive Maintenance of VRLA Batteries in UPS towards Reliable Data Centers}},
  booktitle = {IFAC-PapersOnLine},
  year = {2020},
  doi = {10.1016/j.ifacol.2020.12.854},
}

Loading related content...