Performance Analysis of Three-Phase Phase-Locked Loops for Distorted and Unbalanced Grids

Kai Li, Bo An, Hong Zheng, Ningbo SunJournal of Power Electronics 2017 · DOI

Abstract

This paper studies the performances of five typical Phase-locked Loops (PLLs) for distorted and unbalanced grid, which are the Decoupled Double Synchronous Reference Frame PLL (DDSRF-PLL), Double Second-Order Generalized Integrator PLL (DSOGI-PLL), Double Second-Order Generalized Integrator Frequency-Lock Loop (DSOGI-FLL), Double Inverse Park Transformation PLL (DIPT-PLL) and Complex Coefficient Filter based PLL (CCF-PLL). Firstly, the principles of each method are meticulously analyzed and their unified small-signal models are proposed to reveal their interior relations and design control parameters. Then the performances are compared by simulations and experiments to investigate their dynamic and steady-state performances under the conditions of a grid voltage with a negative sequence component, a voltage drop and a frequency step. Finally, the merits and drawbacks of each PLL are given. The compared results provide a guide for the application of current control, low voltage ride through (LVRT), and unintentional islanding detection.
BibTeX
@article{li2017performance,
  author = {Kai Li and Bo An and Hong Zheng and Ningbo Sun},
  title = {{Performance Analysis of Three-Phase Phase-Locked Loops for Distorted and Unbalanced Grids}},
  journal = {Journal of Power Electronics},
  year = {2017},
  doi = {10.6113/jpe.2017.17.1.262},
}

Loading related content...

Figure