PD Flexible Built-In High-Sensitivity Elliptical Monopole Antenna Sensor

Hanting Zhang, Guozhi Zhang, Xiaoxing Zhang, Hanlu Tian, Changyue Lu, Jianben Liu, Yin Zhang2022

TL;DR

This paper introduces a novel flexible, built-in elliptical monopole antenna sensor designed for detecting partial discharge (PD) in Gas Insulated Switchgear (GIS). The antenna offers high sensitivity and maintains its performance even when bent, addressing limitations of rigid, external sensors and improving PD detection capabilities in critical power infrastructure.

What Problem Does This Paper Address?

Partial discharge (PD) is a critical indicator of insulation faults in Gas Insulated Switchgear (GIS), which are widely used in power systems due to their reliability and compact design. Current methods for detecting PD, particularly the ultra-high frequency (UHF) method, often rely on rigid external sensors. These sensors can have insufficient sensitivity, especially when dealing with the complex internal structures of GIS. Furthermore, existing internal UHF sensors often use rigid bases that are difficult to integrate without modifying the GIS itself, posing a risk to the equipment's electrical field distribution. There's a clear need for a flexible, high-sensitivity internal sensor that can be easily integrated into GIS without compromising its operational integrity.

Methods

The researchers developed a flexible built-in high-sensitivity elliptical monopole antenna. Key techniques employed include:

  • Rectangular Patch Antenna Equivalent Technique: Used to model the elliptical radiation patch.
  • Trapezoidal Ground Plane Technique: Inspired by discone antennas, this technique enhances bandwidth and radiation characteristics.
  • Coplanar Waveguide (CPW) Feed Line Index Asymptotic Linearization: This method is used to achieve impedance matching and expand the antenna's bandwidth by dividing the feed line into numerous stepped sections.
  • Finite Element Simulation (ANSYS HFSS): Used for designing, simulating, and optimizing the antenna parameters, including VSWR and gain under various bending conditions.
  • Flexible Substrate Material (PI): Polyimide (PI) was chosen as the flexible substrate due to its high dielectric constant, low dielectric loss, good insulation, ductility, and flexibility, making it suitable for the demanding GIS environment.
  • Experimental Verification: The antenna's performance was tested on a 220 kV GIS partial discharge experimental platform.

Datasets

Not discussed in the paper. The paper focuses on the design, simulation, and experimental testing of a single antenna prototype.

Key Insights and Ideas

  • Flexibility is Key for Integration: The use of a flexible substrate (PI) is crucial for seamless integration into the curved internal surfaces of GIS without requiring modifications to the GIS structure itself.
  • Bending Doesn't Kill Performance: The antenna demonstrates remarkable resilience to bending, maintaining acceptable VSWR values even at a bending radius of 500 mm, which is significant for real-world GIS applications.
  • Optimized Design for Wideband UHF Detection: The combination of elliptical patch, trapezoidal ground plane, and CPW feed line linearization effectively broadens the antenna's operating bandwidth to cover the entire 300 MHz to 3 GHz UHF range relevant for PD detection.
  • Negligible Impact on GIS Electric Field: Simulations show that the built-in flexible antenna has a negligible impact on the internal electric field distribution of the GIS, addressing a critical safety concern.
  • High Sensitivity for Low PD Levels: The antenna can effectively detect partial discharges as low as 10 pC, which is vital for early fault detection.

Key Results

  • The flexible antenna maintains a VSWR < 3 in the 300 MHz–650 MHz band and VSWR < 2 in the 650 MHz–3 GHz band, even with bending radii of 0, 100, 300, and 500 mm.
  • The antenna can detect PD signals with an average discharge amount below 10 pC.
  • Simulations confirmed that the built-in antenna has a negligible effect on the internal electric field distribution of the GIS.
  • Experimental tests showed the antenna can effectively detect PD signals at different voltage levels (12.5 kV and 13.6 kV).
  • The antenna's time-domain and frequency-domain characteristics were analyzed, showing effective detection of UHF electromagnetic pulse signals from 1 GHz to 1.5 GHz, even in the presence of external interference.

Limitations and Future Work

  • External Interference: While the antenna is designed for high sensitivity, the paper acknowledges that external electromagnetic interference (e.g., from 4G signals) can affect measurements, requiring careful filtering and analysis.
  • Production Precision: Minor differences between simulated and measured VSWR in the low-frequency band are attributed to antenna production and welding process precision, as well as unavoidable metal conductor interference during testing.
  • Future Work: The paper suggests further research into the antenna's gain and sensitivity by comparing it with other built-in UHF PD detection antennas. The authors also mention the need for further optimization of parameters to achieve miniaturization. The study also implies that further validation in diverse GIS environments and under various fault conditions would be beneficial.

Summary updated

BibTeX
@misc{zhang2022pd,
  author = {Hanting Zhang and Guozhi Zhang and Xiaoxing Zhang and Hanlu Tian and Changyue Lu and Jianben Liu and Yin Zhang},
  title = {{PD Flexible Built-In High-Sensitivity Elliptical Monopole Antenna Sensor}},
  year = {2022},
  doi = {10.3390/s22134982},
}
Figure