Abstract
This study proposes a distributed power line sensing system based on Orthogonal Chirp-Division Multiplexing (OCDM) and Time-Domain Reflectometry (TDR). By leveraging the convolution theorem of the modified discrete Fresnel transform (DFnT), the authors introduce a multiple access scheme that enables simultaneous reflectometric and transferometric sensing across multiple power line modems (PLMs). The system's performance is evaluated in terms of range resolution, maximum unambiguous range, measurement density, and signal-to-interference-plus-noise ratio (SINR). Numerical results demonstrate that the OCDM-based approach maintains a high measurement frequency regardless of the number of modems, providing a significant advantage over traditional time-division and code-division multiple access schemes while ensuring fair performance across the network.
Introduction
Maintaining the health of modern power grids requires continuous monitoring to detect "soft" faults, such as cable degradation or high-impedance faults, which can lead to catastrophic failure if left unaddressed. Time-Domain Reflectometry (TDR) is a standard technique for this purpose, involving the injection of signals into the line and the analysis of their reflections. However, implementing TDR in a distributed manner across an entire network is challenging due to interference between multiple sensing units. Existing Orthogonal Frequency-Division Multiplexing (OFDM) solutions often face trade-offs between measurement frequency and performance consistency across different frequency bands.
System Model and OCDM-Based Sensing
The proposed system utilizes a baseband version of OCDM, which replaces the Discrete Fourier Transform (DFT) used in OFDM with the Discrete Fresnel Transform (DFnT). Specifically, a Modified DFnT (Type III) is employed to ensure the generated signals are real-valued, making them compatible with baseband power line communication (PLC) systems.
To enable multiple access without interference, the authors propose a "subchirp allocation" scheme in the Fresnel domain. Instead of separating modems by time or frequency, they are assigned orthogonal subchirps. This allows the system to perform both reflectometry (analyzing reflections) and transferometry (analyzing signals between modems) simultaneously.
Performance Analysis and Key Results
The study evaluates the OCDM-based TDR system using numerical simulations of typical European low-voltage (LV) and US medium-voltage (MV) power distribution networks.
Measurement Density
A primary advantage of the OCDM scheme is its ability to maintain a constant, high number of measurements (snapshots) per second as more modems are added to the network. In contrast, Time-Division Multiple Access (TDMA) and Code-Division Multiple Access (CDMA) schemes see a sharp decline in measurement frequency as the number of PLMs ($N_{PLM}$) increases. For a network with 10 modems, OCDM provides approximately ten times more reflectograms per second than TDMA.
Fairness and Resolution
In frequency-division (FDMA) schemes, modems assigned to higher frequencies often suffer from increased attenuation and noise. Because OCDM spreads chirps across the entire available bandwidth, every modem experiences the same average channel conditions. This results in a "fair" and stable SINR across the network—measured at 14.85 dB in a Brazilian MV scenario, compared to the fluctuating 13.83–16.04 dB range seen in FDMA. Furthermore, OCDM achieves the same range resolution as OFDM-based systems, as resolution is fundamentally determined by the signal bandwidth ($B$).
Sensing Range
The maximum unambiguous range for reflectometry was calculated to be approximately 1.87 km for LV scenarios and 3.21 km for MV scenarios (with a cyclic prefix of 30). However, the authors noted that this range is more sensitive to the measurement window length in OCDM than in TDMA; as more modems are added, the effective window for each modem shrinks, which can eventually limit the maximum detectable distance.
Conclusion
The proposed OCDM-based multiple access scheme offers a robust solution for distributed power line sensing. By providing high measurement density and fair performance across all network modems without sacrificing spatial resolution, it outperforms traditional TDMA and CDMA approaches. Future work will focus on experimental validation using physical PLC hardware and the development of data fusion techniques to integrate high-density measurements into comprehensive grid health maps.
Summary updated