Optimization of Low Frequency Load Shedding for Isolated Power System Based on Wide Area Measurement System

Xiang ChenEast 2011

Abstract

The successive approximation method which removes load step by step with delay is often used in low frequency load shedding,but often causes over-shedding,under-shedding and many other problems.This paper proposes niche technology-based NSGA-II algorithm to optimize low-frequency load shedding.And in order to minimize the total removed load within the requirement for system frequency recovery,inertial central frequency,based on wide area measurement system,is used as the signal to start up load shedding.Meanwhile,some influencing factors should be taken into account: features of load frequency,importance of different load points,and coordination between system frequency recovery and the generator frequency protection.Finally,simulation results show the effectiveness of this program.