Optimal coordinated PET and generator excitation control for power systems

Fan Shu, Chengxiong Mao, Luonan ChenInternational Journal of Electrical Power & Energy Systems 2006 · DOI

TL;DR

This paper introduces a novel coordinated control strategy for Power Electronic Transformers (PETs) and synchronous generator excitation systems to enhance power system transient stability. By leveraging the flexible control capabilities of PETs, the proposed method significantly improves system damping and voltage regulation compared to conventional approaches.

What Problem Does This Paper Address?

Traditional power systems rely on generator excitation controllers and governors to maintain stability during disturbances. However, governors are often too slow to be effective in transient scenarios, and while excitation control helps, it may not always guarantee stability. Conventional transformers are passive components with no inherent control function. This paper addresses the need for more robust and responsive control mechanisms in power systems, particularly in the face of increasing complexity and the integration of new technologies. The authors propose the use of Power Electronic Transformers (PETs) as a means to actively control voltage and power flow, thereby enhancing system stability.

Methods

The authors propose an optimal coordinated control strategy for a generator-PET unit. The core of their approach involves:

  • Power System Modeling: They develop a single-machine-infinite-bus (SMIB) system model that incorporates a generator and a PET. This model includes state variables such as power angle, angular velocity, generator terminal voltage, and PET DC bus voltage, along with control variables like generator excitation voltage and PET voltage source converter (VSC) modulation index and phase angle.
  • PET Model: The PET is modeled using a DC-link configuration, which allows for flexible control of voltage and current through Pulse Width Modulation (PWM) technology. The model simplifies by ignoring electromagnetic switching transients and power electronic device losses.
  • Optimal Control Design: A linear quadratic regulator (LQR) approach is employed to derive an optimal coordinated control law. This involves transforming the system dynamics and defining an objective function to minimize, leading to a feedback control law that coordinates the PET and generator excitation.
  • Simulation and Comparison: The proposed controller is evaluated through numerical simulations on the SMIB system. Its performance is compared against a conventional generator-transformer unit equipped with an Automatic Voltage Regulator (AVR) and Power System Stabilizer (PSS) controller.

Datasets

Not discussed in the paper. The study relies on a simulated SMIB system with parameters provided in Appendix A.

Key Insights and Ideas

  • PET as an Active Stabilizer: The paper demonstrates that PETs are not just passive transformers but can be actively controlled to significantly improve power system transient stability.
  • Coordinated Control Advantage: The synergy between PET control and generator excitation control is crucial. The PET's ability to rapidly adjust voltage and phase angle, combined with the generator's excitation, provides a more effective damping mechanism than conventional methods.
  • Improved Dynamic Performance: The PET-based coordinated control leads to reduced oscillations in power angle and speed, and faster settling times for voltage during various disturbances.
  • Flexibility of PET: The paper highlights that PETs can enable generators to operate at a unit power factor, potentially improving generator efficiency. They also offer capabilities like acting as a circuit breaker.

Key Results

The simulations show that the proposed optimal coordinated PET and generator excitation controller outperforms the conventional AVR+PSS controller in terms of transient stability for several disturbances:

  • 5% Voltage Step Increase: The PET-based system exhibits significantly smaller oscillations in power angle and speed, with voltage reaching its steady state much faster.
  • Three-Phase to Ground Fault: The coordinated controller damps oscillations much faster and improves terminal voltage performance compared to the conventional approach.
  • Opening/Closing of Transmission Line: Similar improvements in damping and voltage regulation are observed for this disturbance.

Limitations and Future Work

  • Limitations:
    • The study is based on a simplified Single-Machine Infinite-Bus (SMIB) system.
  • Electromagnetic switching transients and losses of power electronic devices are ignored in the model.
  • The analysis assumes ideal conditions for PWM control (sufficiently large carrier wave ratio).
  • Future Work:
    • The authors suggest extending the research to multi-machine systems to further investigate the effectiveness of PET on more complex power grids.
  • Further examination of PET's effectiveness from both theoretical and computational viewpoints is proposed.
  • The paper also briefly mentions PET's potential for addressing issues like power quality, connecting distributed energy resources, and enabling asynchronous operation of synchronous generators, suggesting these as areas for future exploration.

Summary updated

BibTeX
@article{shu2006optimal,
  author = {Fan Shu and Chengxiong Mao and Luonan Chen},
  title = {{Optimal coordinated PET and generator excitation control for power systems}},
  journal = {International Journal of Electrical Power \& Energy Systems},
  year = {2006},
  doi = {10.1016/j.ijepes.2005.11.001},
}
Figure