NeurIPS 2026Coming to NeurIPS?Explore papers, orals & directions

Optimal configuration of cooperative stationary and mobile energy storage considering ambient temperature: A case for Winter Olympic Game

Meng He, Hongjie Jia, Tao Xu, Wei Wei, Yuhan Wu, Lemeng Liang, Shuqi Cai, Zuozheng Liu, Rujing Wang, Mengchao LiApplied Energy 2022

Abstract

Mega-events like the Winter Olympics increasingly aim for carbon neutrality, relying heavily on renewable energy generation. However, the intermittency of renewables and the extreme reliability requirements of such events often lead to over-provisioning of stationary energy storage, resulting in "stranded assets" once the event concludes. This paper proposes a two-stage optimization framework that combines permanent Stationary Energy Storage Systems (SESS) with temporary, rented Mobile Energy Storage Systems (MESS). Crucially, the model incorporates the thermal dynamics of containerized batteries to account for performance degradation caused by extreme cold ambient temperatures.

Introduction

The transition to carbon-neutral mega-events necessitates high-reliability power grids supported by renewable energy. Because renewable generation is intermittent, energy storage is essential for broadcasting, lighting, and transportation. However, sizing permanent storage solely for short-term peak event loads leads to excessive capital costs and underutilized infrastructure post-event. Furthermore, in cold climates typical of the Winter Olympics, lithium-ion battery performance is significantly degraded due to increased charge-transfer resistance. This research addresses these challenges by optimizing a mix of permanent SESS and rented MESS while actively modeling the thermal management of battery containers.

Methodology

The proposed framework utilizes a two-stage joint optimization model to balance grid reliability, capital costs, and battery health:

  1. Stage 1 (Long-term SESS Planning): Optimizes the permanent capacity and power of SESS to minimize annualized Life Cycle Cost (LCC) while maximizing arbitrage and loss-reduction revenues during normal operations.
  2. Stage 2 (Short-term MESS Planning): Determines the number of rented MESS units required specifically for the high-demand event period, ensuring critical loads remain powered during peak scenarios.

A key innovation is the inclusion of a thermal management model for the Container Energy Storage System (CESS). This model tracks the heat balance—considering battery self-heating, ambient temperature, and active HVAC systems—to manage battery degradation and operational costs.

Internal components of a Container Energy Storage System (CESS) including thermal management units.

The optimization is solved using a hybrid Genetic Algorithm and Simulated Annealing (GA-SA) for sizing, while the operational dispatch is formulated as a Mixed-Integer Second-Order Cone Programming (MISOCP) problem for efficient solving.

Results and Discussion

The model was validated using a simulated 21-node hybrid distribution system modeled after a Winter Olympic venue across winter, summer, and event-day scenarios.

  • Economic Viability: The SESS configuration was found to be net-profitable (approximately $26,857/year) by leveraging electricity price arbitrage and reducing network transmission losses.
  • MESS Efficiency: Renting MESS for the 60-day event period effectively managed peak loads without requiring permanent over-sizing of the SESS. Rental fees accounted for approximately 68% of mobile storage costs, but prevented massive capital investment in permanent infrastructure.
  • Thermal Impact: In extreme cold, active HVAC heating is necessary as battery self-heat is insufficient to maintain optimal operating ranges. Conversely, in summer, natural ventilation can handle most cooling needs, reducing parasitic electricity costs.
  • Grid Stability: The joint SESS+MESS configuration eliminated voltage violations during peak hours and provided essential emergency backup power for critical nodes.

Conclusion

Integrating mobile and stationary energy storage provides a cost-effective and reliable solution for mega-events. By explicitly modeling thermal management and battery degradation, organizers can optimize infrastructure investments, ensuring both event-time reliability and long-term economic sustainability. Future work will focus on incorporating stochastic renewable generation and integrating electric vehicle fleets into the grid model.

Summary updated

BibTeX
@misc{he2022optimal,
  author = {Meng He and Hongjie Jia and Tao Xu and Wei Wei and Yuhan Wu and Lemeng Liang and Shuqi Cai and Zuozheng Liu and Rujing Wang and Mengchao Li},
  title = {{Optimal configuration of cooperative stationary and mobile energy storage considering ambient temperature: A case for Winter Olympic Game}},
  year = {2022},
  eprint = {2202.09761},
  archivePrefix = {arXiv},
  url = {https://arxiv.org/abs/2202.09761},
}
Figure