Monitoring modeling and analysis of the electromagnetic environment of HVDC transmission lines based on ion flow and wind coupling field

Z. H. Qin, Jiong Chen, Maoxin Ren, Fan YinFrontiers in Energy Research 2025 · DOI

Abstract: High-voltage direct current transmission lines are an integral part of the power system, but the ion flow field and total electric field they generate can be harmful. Moreover, two of the most critical indicators for evaluating environmental compatibility, ion current density $\rho_j$ and total electric field strength $E$, can be affected by wind. The difficulty in monitoring and modeling the ion flow and wind coupling field has caused recent research to consider only transverse winds and not take into account the wind directions. As a result, it cannot model the actual situation accurately for monitoring and analysis. For this reason, this article takes the ±800 kV Jinsu Line in Huzhou as an example and constructs a 3-D monitoring model using the finite element method. The nonlinear mapping relationship between the model design parameters and the feature parameters is approximated by an extreme learning machine, and the actual measurement results are used to invert the model design parameters to modify the finite element model and realize the precise monitoring of the $\rho_j$ and $E$ in different wind speed and direction situations. The results show that the modified model can realize the condition monitoring of the electromagnetic environment of transmission lines with an improved accuracy of 20.86%. In addition, some laws are discovered: the peak absolute values of $\rho_j$ and $E$ increase and then decrease with the increase in wind speed; at low wind speed, the smaller the included angle between the wind direction and the line direction is, the smaller the peaks are; at high wind speed, the smaller the included angle is, the peaks increase and then decrease.

Introduction: The Invisible Impact of HVDC Lines

High-voltage direct current (HVDC) transmission lines are essential for long-distance power distribution, but they produce a complex electromagnetic environment. When the voltage exceeds a certain threshold, the surrounding air ionizes—a phenomenon known as the corona effect. This creates a flow of ions toward the ground, characterized by ion current density ($\rho_j$) and total electric field strength ($E$).

Accurately monitoring these parameters is vital for environmental safety. However, real-world conditions involve wind, which significantly alters ion distribution. Previous research often simplified this by considering only transverse winds (perpendicular to the lines), failing to account for varying wind directions and speeds. This study addresses this gap by developing a 3-D monitoring model that couples ion flow with realistic wind vectors.

Methodology: 3-D Modeling and Wind Coupling

To capture the spatial complexity of the electromagnetic environment, the researchers constructed a 3-D model using the Finite Element Method (FEM), specifically focusing on the ±800 kV Jinsu Line in Huzhou, China. Unlike traditional 2-D models, this approach accounts for the three-dimensional nature of the ion flow and incorporates a "wind shear" function to reflect how wind speed increases with altitude.

Boundary delimitation for the 3-D monitoring model, showing wind vectors and angular directions.

The core of the methodology involves a hybrid approach that integrates physics-based simulation with machine learning. The researchers used an Extreme Learning Machine (ELM) neural network to approximate the nonlinear mapping between model design parameters and feature parameters. This allowed them to use actual field measurements to "invert" and modify the FEM model, correcting for inherent simulation errors.

Flowchart of the proposed monitoring and model modification process.

Key Results and Environmental Laws

The integration of ELM and FEM yielded significant improvements in monitoring performance:

  • Accuracy Improvement: The modified model improved monitoring accuracy by 20.86% compared to the initial model.
  • Error Reduction: The average relative error was reduced from 34.13% to 13.27%.
  • Wind Direction Sensitivity: The study confirmed that ignoring wind direction leads to substantial errors (over 34% on average), proving that the angle between the wind and the line is a critical variable.

Furthermore, the research identified specific "laws" governing the ion flow field:

  1. Non-linear Peak Values: The peak absolute values of $\rho_j$ and $E$ follow an "increase then decrease" pattern as wind speed rises.
  2. Angular Influence: At low wind speeds, smaller angles between the wind and the line result in lower peaks. At high wind speeds, smaller angles cause peaks to increase and then decrease.
  3. Maximum Hazard Scenario: The highest peak absolute values were observed at a wind speed of approximately 4.4 m/s.

Conclusion

By combining 3-D FEM modeling with ELM-based inversion, this research provides a high-precision tool for monitoring the electromagnetic environment of HVDC lines. The model's ability to account for varying wind directions and speeds represents a significant advancement over previous transverse-only models. Future work will aim to incorporate more complex conductor systems and additional weather variables like humidity to further refine environmental monitoring.

Summary updated

Abstract

High-voltage direct current transmission lines are an integral part of the power system, but the ion flow field and total electric field they generate can be harmful. Moreover, two of the most critical indicators for evaluating environmental compatibility, ion current density ρ j and total electric field strength E , can be affected by wind. The difficulty in monitoring and modeling the ion flow and wind coupling field has caused recent research to consider only transverse winds and not take into account the wind directions. As a result, it cannot model the actual situation accurately for monitoring and analysis. For this reason, this article takes the ±800 kV Jinsu Line in Huzhou as an example and constructs a 3-D monitoring model using the finite element method. The nonlinear mapping relationship between the model design parameters and the feature parameters is approximated by an extreme learning machine, and the actual measurement results are used to invert the model design parameters to modify the finite element model and realize the precise monitoring of the ρ j and E in different wind speed and direction situations. The results show that the modified model can realize the condition monitoring of the electromagnetic environment of transmission lines with an improved accuracy of 20.86%. In addition, some laws are discovered: the peak absolute values of ρ j and E increase and then decrease with the increase in wind speed; at low wind speed, the smaller the included angle between the wind direction and the line direction is, the smaller the peaks are; at high wind speed, the smaller the included angle is, the peaks increase and then decrease.