Measurement of Magnetic and Magnetostrictive Characteristics of Transformer Core Based on Triaxial Strain Gauge and B-H Vector Sensor

Zhen Wang, Zheming Fan, Xiang Li, Kai Xu, Runjie Yu2023 · DOI

TL;DR

This paper presents a novel experimental setup for measuring the local magnetic and magnetostrictive characteristics of transformer cores, particularly under DC bias conditions. By combining triaxial strain gauges with a self-developed B-H vector sensor, the researchers gain a deeper understanding of how these properties vary across different regions of the core, crucial for mitigating transformer vibration and noise.

What Problem Does This Paper Address?

Transformer cores are essential components in electrical systems, and their magnetostrictive properties—the change in shape due to magnetic fields—are a primary source of vibration and noise. While the magnetostriction of individual steel sheets is well-studied, the behavior of a complete, laminated transformer core is far more complex due to interactions between laminations and varying magnetization patterns. Furthermore, real-world transformers can experience DC bias (an unwanted DC component in the magnetic field), which significantly exacerbates magnetostriction and can lead to core damage. Existing research often focuses on single sheets or lacks detailed local measurements within a complete core, especially under DC bias. This paper aims to bridge this gap by providing a detailed, localized analysis of magnetostrictive and magnetic properties in a transformer core, including the critical impact of DC bias.

Methods

The researchers developed a specialized testing system for a two-limb, one-phase transformer core constructed from 12 layers of grain-oriented electrical steel sheets. Key components of their methodology include:

  • Triaxial Strain Gauge System: This system, using KFG-5-120-D17-11 strain gauges, measures in-plane magnetostrictive strain along three directions (0°, 45°, and 90°) relative to the material's rolling direction. The strain signals are amplified and processed using a LabVIEW interface.
  • Self-Developed B-H Vector Sensor: This sensor is designed to measure local magnetic flux density (B) and magnetic field strength (H) simultaneously in two orthogonal directions. It utilizes Hall elements and induced EMF measurements to capture the magnetic behavior at specific points on the core.
  • Experimental Setup: A power amplifier drives the transformer core windings with AC excitation, and optionally, a DC bias current. The system allows for the simultaneous measurement of both magnetic and magnetostrictive signals at six predefined points on the core (yoke, limb, and corner).
  • DC Bias Investigation: The effect of DC bias was studied by applying DC currents of 0.2 A, 0.5 A, and 0.9 A along with the AC excitation.
  • Clamping Position Analysis: The influence of clamping pressure on magnetostriction was investigated by applying a 0.5 kN pressure using wooden plates at different positions on the core.

Datasets

Not discussed in the paper. The study relies on experimental measurements from the constructed transformer core.

Key Insights and Ideas

  • Localized Magnetostriction is Crucial: The study highlights that magnetostrictive strain is not uniform across a transformer core. The corner regions exhibit significantly higher strain compared to the yoke and limb.
  • DC Bias Amplifies Magnetostriction: The presence of DC bias substantially increases magnetostrictive strain, particularly in the limb regions. This is a critical finding for understanding and mitigating damage in transformers operating under non-ideal conditions.
  • Clamping Position Matters: The placement of clamps on the core significantly influences magnetostriction. Fixing clamps in the middle of the yoke reduces overall strain, especially in the corner regions, suggesting a practical method for noise and vibration reduction.
  • Rotational Magnetization in Corners: The B-H vector sensor revealed rotational magnetization patterns in the corner regions, which is a key contributor to the elevated magnetostriction observed there. This is a more complex magnetic phenomenon than simple linear magnetization.
  • Laminated Core vs. Single Sheet: The magnetostrictive strain in a laminated core is generally higher than in a single sheet, with the amplification increasing with magnetization intensity and DC bias. This underscores the importance of studying the core as a whole.

Key Results

  • The strain at the corner area was found to be approximately 1.8 times higher than on the limb and yoke under specific conditions.
  • Under DC bias, the strain at "point 1" (limb) increased by up to 50% with a 0.9 A DC component, while "point 4" (corner) increased by about 30%.
  • The amplification of magnetostrictive strain in the laminated core compared to a single sheet could reach up to 42.2% under certain magnetization and DC bias conditions.
  • Fixing clamps in the middle of the yoke (position "B") resulted in reduced strain in the corner region compared to other positions.

Limitations and Future Work

  • Limited Core Configuration: The study focused on a specific two-limb, one-phase transformer core with a multistep-lap construction. Future work could explore other core geometries and lamination types.
  • Experimental Scope: While the study provides valuable localized measurements, it is an experimental investigation. Further validation through finite element modeling (FEM) could complement these findings.
  • DC Bias Magnitude: The DC bias levels tested were specific. Investigating a wider range of DC bias currents could provide a more comprehensive understanding of its impact.
  • Vibration and Noise Correlation: While magnetostriction is a primary cause of vibration and noise, this paper focuses on measuring the strain itself. Future research could directly correlate these measured strains with actual vibration and acoustic noise levels.
  • Practical Applications: The authors suggest that this research can aid in more accurate calculations of vibration deformation in electrical equipment and provide a basis for developing effective vibration and noise reduction strategies.

Summary updated

BibTeX
@misc{wang2023measurement,
  author = {Zhen Wang and Zheming Fan and Xiang Li and Kai Xu and Runjie Yu},
  title = {{Measurement of Magnetic and Magnetostrictive Characteristics of Transformer Core Based on Triaxial Strain Gauge and B-H Vector Sensor}},
  year = {2023},
  doi = {10.3390/s23135926},
}
Figure